Static switches, Series ss, Series specific information 6u – Schaefer Series SS User Manual

Page 4

Advertising
background image

www.schaeferpower.de

Inverters

Static Switches

with 1-phase output from 0.8 to 10kVA

AC output

AC supply 1

AC supply 2

static switch

1-phase

Inverters

Frequency Designation

.4
.5
.6
.8

400 Hz
50 Hz
60 Hz
800Hz

= natural convection

Model

Output Power [kVA]

Cooling

Input / Output [V]

SS 1506
SS 3506
SS 3516
SS 3526
SS 3536

0.8
1.6

3
5

10





115

SS 1508
SS 3508
SS 3518
SS 3528
SS 3538

0.8
1.6
3.2

5

10





230

Series SS

Static Switches

Series specific information

6U

Eurocassette

(pluggable module for 19“ sub-rack)

Wall mount

21TE

6U

166.5 mm

140 mm

360 mm

260 mm

approx. 3.3 kg

approx. 6.3 kg

series SS 15xx

series SS 15xx

Standard

Optional

Eurocassette

(pluggable module for 19“ sub-rack)

Standard

21TE

6U

226 mm

approx. 5.0 kg

series SS 35xx

Optional

Wall mount

140 mm

360 mm

260 mm

approx. 8.0 kg

series SS 35xx

Function

The Static Switch has two inputs for load supply, a priority and a non-

priority input, and synchronizes the frequency of one supply to the

other. Typically, but not exclusively, supplied by Mains and an Inverter,

there are 3 modes of operation:

1. Service mode Mains - mains is selected as the load provider.

2. Service mode Inverter - inverter is selected as the load provider.

3. Automated function with priority selection.

In the automated function the supply of the priority input is connected

to the load. If the static switch detects deviation from tolerance through

monitoring, it will transfer the load to the non-priority input. When the

supply of the priority input has returned to be within parameters of

voltage and frequency, the static switch reverses this selection.

For adapting the static switch to different requirements, the priority

for mains or inverter operation can be selected externally via an opto-

coupler. The static switch can also be inhibited via another opto-coupler

for disconnecting the load. LEDs and potential-free relay contacts

indicate the mode of operation and / or the status of alarms.

Indication of operation mode

Input / Output

Surge current

5 x I

nom

for 1 s

Overload protection

For models with I

nom

≤ 15 A: short circuit

protected: unit switches off at output

current above 15 A;

For models with I

nom

> 15 A: an external

fuse with slow characteristic is required

Inhibit (remote on / off)

logic low = 0 – 5 V;

logic high = 12 – 30 V

via opto-coupler

Priority selection

logic low = 0 – 5 V;

logic high = 12 – 30 V

via opto-coupler

Transfer trigger

0.8 x U

nom

< voltage < 1.15 x U

nom

Transfer time

- mains to inverter (mains

priority) or inverter to

mains (inverter priority)

For models with I

nom

≤ 15 A:

≤ ½ period, typically ¼ period

(including failure detection time)

For models with I

nom

> 15 A:

one period, typically ½ period

(including failure detection time)

- return to mains (mains

priority) or return to

inverter (inverter priority)

For models with I

nom

≤ 15 A:

practically no interruption

For models with I

nom

> 15 A:

typically ½ period

Options

Mechanics / environment

19” sub-rack for eurocassette,

refer to page 121

Wall mount

Increased mechanical strength

Tropical protection

Extended temperature range to

–40 °C

Green

LED

Red
LED

potential

free contacts *)

Mains operation

Inverter operation

Inverter synchronous with
mains

Mains over voltage

Mains under voltage

Inverter over voltage

Inverter under voltage

Common alarm

Service mode

*) U

max

= 250 VAC, I

max

= 3 A

SS 3506

1.6

SS 3526

5

SS 3508

1.6

SS 3528

5