Van Air Systems FR-1200 User Manual

Page 12

Advertising
background image

PAGE 12

10.1 TROUBLESHOOTING

The following check list should be used as a guideline for troubleshooting problems. Each of the topics will reference other sections in this
manual for further information.

TROUBLESHOOTING

SECTION 10

IS THE POWER ON?

Check the main power source. Make sure the Power switch is in

the

ON position.

IS THE SYSTEM PRESSURIZED?

The dryer system is designed to operate at 60 to 175 psig.

Check to make sure the air supply was connected to the dryer

system inlet.

Check the Differential Pressure indicator on the prefilter. If the

needle is in the RED zone, replace the element.

IS THE DRYER CYCLING?

• IS THE FAILURE TO SWITCH ALARM ACTIVATED?

If the dryer system is not cycling the FAILURE TO SWITCH

ALARM should be activated. The dryer system should be

checked to determine the cause of switching failure.

• IS THERE CONTROL AIR PRESSURE, 60 PSIG MINIMUM?

Make sure that the dryer system inlet pressure is above 60 PSIG.

Replace control air filter element. Reference

SECTION 9.4 for

element replacement instructions.

• IS THE Y-STRAINER PLUGGED?

If the Y-strainer is clogged, their may not be enough control air

pressure to operate the dryer system. Disassemble and clean the

Y-strainer per

SECTION 9.8.

• DO THE SEPARATOR/PREFILTER, PREFILTER, &
AFTERFILTER ELEMENTS NEED CHANGED?

Check the differential pressure gauge on the prefilter and

afterfilter. If the needle on either gauge is in the red zone, replace

the element in that filter. Reference

SECTION 9.7 for details.

• ARE THE PILOT VALVES FAULTY? (SV1 & SV2)

Reference

SECTION 10.3 for procedures to check the operation

of the 3-way valves.

Replace any faulty 3-way valves.

• IS THE INLET VALVE FAULTY?

Reference

SECTION 10.4 for procedures to check the operation

of the inlet transfer valve.

Rebuild or replace the inlet valve as necessary. Reference

SECTION 11.3 for valve repair kit details.

• IS A PURGE EXHAUST VALVE FAULTY?

Reference

SECTION 10.5 for procedures to check the operation

of the purge exhaust valves.

Rebuild or replace the faulty purge exhaust valve. Reference

SECTION 11.3 for valve repair kit details.

• IS AN OUTLET CHECK VALVE FAULTY?

Reference

SECTION 10.6 for procedures to check the operation

of the outlet check valves.

If a valve is faulty, replace it.

• IS THE PURGE METERING VALVE SET PROPERLY?

Reference

SECTION 5.2 for purge metering valve settings and

procedures.

If the purge metering valve requires adjustment, follow the

procedures in

SECTION 5.2.

• IS THE SMARTRELAY FUNCTIONING?

See

SECTION 10.2 for explanation of Smart Relay operation.

IS THE VISIBLE MOISTURE INDICATOR BLUE?

Reference

SECTION 6.3 for an explanation of operation for the

moisture indicator.

• IS THE BLEED ORIFICE FITTING OR SINTERED MUFFLER ON

THE MOISTURE INDICATOR CLOGGED?

Inspect the bleed orifice fitting and the sintered filter on the back

of the moisture indicator. They can be cleaned or replaced.

IS THE DEW POINT ACCEPTABLE?

• ARE THE INLET CONDITIONS WITHIN THE SPECIFICATIONS?

Reference

SECTION 3.1 for the inlet conditions of the dryer

system.

Correct the inlet conditions if necessary. Excessive inlet flow will

greatly reduce the performance of the dryer system.

• IS THE PURGE METERING VALVE SET PROPERLY? Reference

SECTION 5.2 for purge metering valve settings and procedures.

Adjust purge metering valve as required.

• WAS THE DESICCANT INSTALLED?

Is there desiccant in the towers. Reference

SECTION 9.3 for

desiccant replacement procedures.

• IS THE DESICCANT CONTAMINATED WITH LUBRICANTS?

Check the condition of the desiccant bed. If the bed is

contaminated with lubricants, replace the desiccant following the

procedures in

SECTION 9.3.

• IS THE DESICCANT CONTAMINATED WITH MOISTURE?

If the dryer system was operated under excessive inlet conditions,

the desiccant bed may be saturated with liquid moisture. Check

upstream equipment such as aftercoolers. Check the actual

inlet conditions, correct them and condition the bed following the

procedures in

SECTION 5.5.

• IS THE SEPARATOR/PREFILTER DRAINING PROPERLY?

Manually open the drain on the separator to ensure that it is not

flooded. (See PDV-500T manual attached for automatic drain

operation).

• IS THE PREFILTER DRAINING PROPERLY?

Manually open the drain on the pre-filter to ensure that it is not

flooded.

• IS THE FAN MOTOR ON THE PRECOOLER OPERATING?

Check the regulator setting for the air supply to the motor. See

SECTION 5.4 for details. Check the air motor and repair or

replace as necessary.

• ARE THE PURGE MUFFLERS CLOGGED?

Check the tower pressure gauge during the regeneration cycle. If

the tower pressure is above 5 PSIG, replace the purge mufflers.

See

SECTION 11.3 for part number.

• IS THE PRECOOLER DIRTY?

Inspect the outside of the core for dirt and /or oil deposits. If the

core is dirty, clean it per

SECTION 9.6. If the outside of the core

is clean, the inside may be coated with oil. If the inside is coated

with oil the precooler will have to be cleaned per

SECTION 9.7.

IMPORTANT

Leave prefilter valve slightly cracked open to allow for constant

draining or drain the prefilter daily.

Advertising