5 INSPECTION & MAINTENANCE

5.1 Daily Inspection

• Check the physical condition of the power cords, indicating lamps, switches, and the

control enclosure. If any deficiencies are observed, contact your supervisor or O.S.
Walker.

• Check the integrity of the enclosure by inspecting for dust, debris, and fluid. Make

necessary repairs.

• Keep the outside of the enclosure free of dust and debris.

5.2 Having a Problem with your Chuck Control?

Problem Probable

Cause

Solution

BEFORE PROCEEDING, DE-ENERGIZE THE

CONTROL UNIT.

a) Verify the chuck power rating does not

exceed the control's power rating.

b) Disconnect the chuck from the control unit

and verify that the chuck's coil windings are
not shorted.

c) Repair/replace where required.
d) With the load disconnected, re-energize

equipment and cycle through all operating
modes, verifying proper operation.

e) Repeat step d. with the load reconnected.

1. All the remote

unit lights are
flashing.

The load is drawing
excessive current and
the control unit has
protected itself by
disabling all operating
modes.

f) Having successfully completed the above

and unit does not function properly, contact
O.S. Walker, Inc.

a) Verify the input voltage to the control unit

(see Installation section 3).

BEFORE PROCEEDING, DE-ENERGIZE THE

CONTROL UNIT.

b) Verify that all fuses are good (see Standard

Interface Diagram section 5.3 for location).
Use only exact replacement fuses to avoid
damaging unit or causing a safety hazard.

c) Verify the wiring between the control unit

and the remote unit (see Standard Interface
Diagram section 5.3).

2. None of the

control unit lights
are illuminated
and it does not
respond to any
operating mode

Input voltage is too low
or wired incorrectly.
Remote unit is not
properly wired.

d) Having successfully completed the above

and the unit does not function properly,
contact O.S. Walker, Inc.