IR-P Infrared Optical Sensor

FOR CLEAR FLUIDS ONLY

Installation and Technical Data Guide

AW Flow Meters 8809 Industrial Drive, Franksville, WI Phone: (262) 884-9800 Fax: (262) 884-9810

Email: [email protected] www.awflowmeters.com

Rev 09/05

IR-PA Sinking Output Circuit

~40 Ohm

SUPPLY

OUTPUT

GROUND

Analog
Switch

• User may need to add external components to interface to

displays or other instruments

• User must limit output voltage to Supply -1V

• Max current sinking capability: 50mA

Supply Voltage:

+10 to 26 Volt DC

Supply Current:

20 mA ± 0.10

Duty Signal:

50% ± 15%

Minimum Signal:

0.5 Hz

Frequency Output:

TBD

Driving Capacity:

50 mA Max resistive load

Output Impedance:

~ 40 Ohm - analog switch and self-resetting fuse

Temperature Range:

-40° F to 185° F (-40° C to 85° C)

Technical Data:

• Signal output square wave:

Vhigh = Supply -1V @ no output load
Vlow = 0.1V

• Max sourced output voltage: Supply -0.5V

• Max current sourcing capabilities: 50mA

~40 Ohm

SUPPLY

OUTPUT

GROUND

Analog
Switch

IR-PB Sourcing Output Circuit