HDT User’s Manual

page 18

Note: ‡ in the factory default mode the HDT is setup using HART Alarm Selection Code
(ref Universal command 15) such that when there are errors the current loop draws 21mA.
However it is also possible to configure it to 4mA, or 20mA, or 3.8mA, or to hold last out-
put

Symptom

(more than 25 sec after powerup)

Possible cause

Remedy

Current

Loop

Pin 3

Fixed at
~3.8mA

High
impedance

Instrument failure

Cycle power, if prob-
lem persists return
instrument

EEPROM checksum
failure

Intermittent
(0V-3V)
1200 baud
RS-232 data

Loop voltage insuffi-
cient

Check power supply's
capability to maintain
at least 5V at 20 mA.
see appendix A

Fixed at

21mA

1. open sensor
2. shorted sensor

Check sensor & cycle
power, if problem per-
sists return instrument

4 to 20 mA

Normal Operation

Fixed at
4mA

Measurement below
HART Command 15
Primary Variable Ana-
log Output Lower
Range

Refer to sensor section

XXX

Fixed at
20mA

Measurement above
HART Command 15
Primary Variable Ana-
log Output Upper
Range

0 mA

High

impedance

1. Cable open
2. Fuse open due to
excessive voltage

1. Check cables
2. Wait for self reset-
ting fuse cooldown.