Figure #3, Figure #2 – Detcon IR-542 User Manual

Page 10

Advertising
background image

3.5.6 Remote Mounting Applications

Some sensor mounting applications require that the gas sensor head be remotely mounted away from the sensor

transmitter. This is usually true in instances where the gas sensor head must be mounted in a location that is diff i-

cult to access. Such a location creates problems for maintenance and calibration activities. Detcon provides the IR-

540/IR-541/IR-542 sensor in a remote-mount conf iguration in which the sensor (Model IR-540-RS, IR-541-RS or

IR542-RS) and the transmitter (Model IR-540-RT, IR-541-RT or IR542-RT) are provided in their own condulet hous-

ing and are interfaced together with a six conductor cable. Shielded cable is required and must be installed in its

own (unshared) conduit (use Alpha Wire Company #6342 cable). A maximum of 100 feet of separation is allowed.

Reference f igure 4 for wiring diagram.

Detcon Model IR-540/IR-542 Carbon Dioxide Sensor PG.10

BLU

YEL

BLK

WHT

mA

VDC Power In

4-20 mA Output

BRN

RED

Sensor

Base Connector Board

Figure #3

4 3/4"

3/4" NPT

1/4" Dia.

Mounting Holes

8 1/4"

6 1/8"
5 1/2"

3/4" NPT

Rainshield/

Splashguard

2"

2 1/8"

Figure #2