Maintenance, Warnings – Edwards Signaling 125 Class Halogen User Manual

Page 2

Advertising
background image

P/N 3101650 ISSUE 3

Figure 2. Panel Mounting

125 Class

Visual Indicator

Gasket

(supplied)

Locking Nut -

1.3625" OD

(supplied)

Control panel

(enclosure)

Wire Nuts

(Not Supplied)

18” Wire Leads

Power Source

Wires

Maintenance

Figure 1. Conduit Mounting (3/4" Shown)

To avoid risk of injury, install lens before

energizing the unit.
To avoid the risk of injury, do not start any

maintenance when unit is energized.
To prevent electrical shock, disconnect all

power and wait five (5) minutes for stored

energy in strobe modules to dissipate

before starting work on unit.

WARNINGS

Cleaning
Disconnect power before cleaning. The module lens exterior

surfaces should be periodically cleaned with a soft clean

cloth using water and a mild detergent to maintain optimum

light visibility.

Lamp Replacement
1. Conduit Mounted Modules: Disconnect wiring and, if

necessary, unscrew base from conduit (Figure 1).

Panel Mounted Modules: Disconnect wiring and

remove locking nut that secures the base to the panel

(Figure 2).

2. Remove (4) screws that secure the lens to the base from

bottom of base (Figure 3) and remove lens.

3. Replace halogen lamp as follows (Figure 3):

a. Grasp the metal base of the halogen lamp and push

the lamp down while turning counterclockwise. Then,

pull the lamp directly upward to remove from the
socket.

b. Grasp the new halogen lamp by its base and insert

in the socket. Push down and rotate clockwise to

lock in place.

CAUTION: Do not touch glass surface of lamp at

any time.)

4. Reattach lens to base and fasten with screws removed

in step 2.

125 Class

Visual Indicator

Power Source

Wires

DC units; Red positive (+)

AC units; Black Hot
DC units; Black negative (-)

AC units; White neutral

Wire nuts

(not supplied)

18” Wire Leads

3/4” NPT external (shown)

1/2” NPT internal

conduit (not supplied)