Specifications, Regulatory information, Contact information – Edwards Signaling Genesis Signal Master Module User Manual

Page 2

Advertising
background image

2 / 2

P/N 3100124 • REV 08 • REB 30JAN13

Figure 3: Horn silence / synchronization using two NACs

1.

NAC 1 horn in

2.

NAC 1 strobe in

3.

Horn resistor, value determined by the control panel

4.

Genesis appliance with Genesis Signal Master

5.

To next appliance. EOL resistor or Class A circuit return

Notes

Polarity shown in alarm condition

The horn circuit can be silenced without turning off strobes

Figure 4: Horn silence / synchronization using one NAC

1.

Signature data circuit from loop controller or previous device

2.

From previous appliance or control panel

3.

Genesis appliance with Genesis Signal Master

4.

To next appliance, EOL resistor or Class A circuit return

5.

To next device or Class A circuit return

Notes

EOL resistor is determined by the control panel requirements

Polarity shown in alarm condition

The horn circuit can be silenced without turning off strobes

CR module must be located in the same electrical box as the
Genesis Signal Master

Specifications

Operating voltage

16 to 33 VDC or 16 to 33 VFWR

Operating current

33 mA

Output rating

2 A max. Actual value limited by system NAC
and power outputs.

Synchronization

Flash

Resistance
between two
appliances


1/s, within 10 ms indefinitely

20 Ω max.

Wire size

12 to 18 AWG (0.75 to 2.50 mm²)

Mounting

Snaps to back of Genesis appliance

Operating environment

Temperature

Relative humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the product serial number
(located on the product identification label) are
the year of manufacture.

UL rating

Regulated 24 DC, Regulated 24 FWR [1]

Synchronization

UL 1971 compliant

Environmental
class

UL: Indoor

North American
standards

UL 1971, UL 1638, UL 464, CAN/ULC S525,
CAN/ULC S526

[1] This module was tested to the regulated 24 VDC/FWR operating
voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these
values for system operation.

Contact information

For contact information, see www.utcfireandsecurity.com.

-

-

+