Maintenance – Edwards Signaling Genesis Temporal Horn User Manual

Page 2

Advertising
background image

2 / 4

P/N 3100558 • REV 04 • REB 30JAN13

Figure 2: Wiring diagram

1

2

-

+

1.

From NAC output

2.

To next NAC output

Note: Polarity is shown in the alarm condition.

Maintenance

Caution: To maintain the required agency listings, do not
change factory applied finishes.

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

Table 2: Sound level output (dBA)

Signal and voltage

Low

High

Temporal

16 VDC

76.0

81.4

24 VDC

79.4

84.4

33 VDC

82.1

86.3

Continuous

16 VDC

80.1

85.5

24 VDC

83.5

88.6

33 VDC

86.5

90.4

UL 464: Sound level output at 10 ft. (3.05 m) measured in a
reverberant room.

Table 3: Sound level output (dBA, temporal tone, peak)

Tonal and voltage

High

16 VDC

98.8

24 VDC

102.7

33 VDC

104.3

16 VFWR

102.4

24 VFWR

105.0

33 VFWR

106.9

CAN/ULC-S525: Meets or exceeds 85 dBA in an anechoic chamber at
10 ft. (3.05 m)

Table 4: Operating current in RMS (A)

Voltage

High

Low

16 VDC

0.026

0.019

24 VDC

0.036

0.027

33 VDC

0.041

0.033

16 VFWR

0.051

0.037

24 VFWR

0.069

0.052

33 VFWR

0.076

0.070

VDC = Volts direct current, regulated and filtered

VFWR = Volts full wave rectified

Table 5: Audible directional characteristics (horizontal pattern)

Angle (°) [1]

Sound output (dBA) [2]

−90

94

−45

97 (−6)

−30

100 (−3 )

90

103

30

100 (3 )

45

97 (6 )

90

96

[1] Angles are measured from a perpendicular axis; positive angles to
the right

[2] Peak output at 24 VDC, set for temporal tone.

Table 6: Audible directional characteristics (vertical pattern)

Angle (°) [1]

Sound output (dBA) [2]

−90

94

−40

97 (−6)

−25

100 (−3)

90

103 dBA

35

100 (3)

45

97 (6)

90

96

[1] Angles are measured from a perpendicular axis; positive angles are
up.

[2] Peak output at 24 VDC, set for temporal tone.

Advertising