Figure 5: UL 1971 minimum light output (% of rating vs. angle)

100

95

90

85

80

75

70

65

60

55

50

45

40

35

30

25

20

15

10

5

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

0

5

10 15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

-5

-10

-15

-20

-25

-30

-35

-40

-45

-50

-55

-60

-65

-70

-75

-80

-85

-90

1

2

1. Angle
2.

Minimum UL required candela light output

____ % of rated candela vertical specification
- - - - % of rated candela horizontal specification

Specifications

Voltage

24 VDC or 24 VFWR nominal

Strobe operating
current

See Table 3

Light output

Selectable at 15, 30, 75, and 110 cd

Sound level output

See Table 4

Default settings
Signal
Sound

level

output
Operation


Steady
High dB

Noncoded

Signals
Steady
Temporal
Coded


60 strokes per minute
3-stroke pattern
Maximum 60 strokes per minute

Operating modes
Noncoded
Coded


Continuous voltage
Single-stroke controlled by voltage

Wire size

12 to 18 AWG (0.75 TO 2.50 mm²)

Compatible electrical
boxes

2-1/2 in. (64 mm) deep single-gang box
4 in. square box 1-1/2 in. (38 mm), 2-gang
4 in. octagonal with G1T or G1RT trim
accessory

Operating environment
Temperature
Relative

humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Table 3: Strobe operating current in RMS (A)

15 cd

30 cd

75 cd

110 cd

VDC

0.099 0.134 0.233 0.277

VFWR

0.154 0.195 0.338 0.383

VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified

Operating currents shown above were measured by UL at 16 VDC and
16 VFWR.

Table 4: ULI Ratings, temporal output (private mode)

Signal High

db

Low

db

Temporal 56.9

52.5

Steady 58.2 52.8

dBA = Decibels, A-weighted

UL464: Sound level output at 10 ft (3.05 m) measured in a reverberant
room at 16 V.

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture

UL rating

Regulated 24 DC and 24 FWR

Environmental
class

UL: Indoor

Synchronization

Meets UL 1971 requirements. Maximum allowed
resistance between any two devices is 20

Ω.

Refer to specifications for the synchronization
control module, this strobe, and the control panel
to determine allowed wire resistance.

Agency listings

Meets UL1638, UL1971 (see Figure 1) and
UL464 (private mode)

Contact information

For contact information, see www.utcfireandsecurity.com.