Maintenance, Specifications, Regulatory information – Edwards Signaling Genesis High Candela Ceiling Speaker-Strobe User Manual

Page 3: Contact information

Advertising
background image

P/N 3100615 • REV 05 • REB 30JAN13

3 / 4

Table 3: Strobe operating current in RMS (A)

95 cd

115 cd

150 cd

177 cd

VDC

0.330

0.392

0.502

0.565

VFWR

0.432

0.518

0.643

0.693

VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified

Operating currents shown above were measured by UL at 16 VDC and
16 VFWR.

Table 4: Sound level output (dBA)

25V (UL)

25V (ULC)

70V (UL)

70V (ULC)

1/4 W

80

78

80

81

1/2 W

84

81

84

81

1 W

87

87

87

87

2 W (UL)

90

91

2.2 W (ULC)

90

90

UL1480: Sound level output at 10 ft (3.05 m) measured in a
reverberant room using 400 to 4,000 Hz band limited pink noise.

Directional characteristics: Within 6 dB of on-axis sound level when
measured 90

° off-axis (horizontal).

Figure 6: Light output profile

Maintenance

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

Do no change the factory-applied finish.

Specifications

Operating voltage

Speaker

Strobe


25 VRMS (model S2) or 70 VRMS (model S7)
24 VDC, 24 VFWR

Supervisory voltage

30 V maximum

Strobe operating
current

See Table 3

Sound level output

See Table 4

Speaker response

400 to 4,000 Hz

Light output

Selectable at 95, 115, 150, and 177 cd

Default settings

1 flash per second (fps)

Wire size

12 to 18 AWG (0.75 TO 2.50 mm²)

Compatible electrical
boxes

North American 4 in. square electrical box,
2-1/8 in. min. deep

Operating environment

Temperature

Relative humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture

UL/ULC rating

Regulated 24 DC, regulated 24 FWR

This device was tested to the regulated
24 DC/FWR operating voltage limits of 16 V and
33 V. Do not apply 80% and 110% of these
values for system operation.

Environmental
class

UL: Indoor dry

Synchronization

Meets UL 1971 requirements. Maximum allowed
resistance between any two devices is 20

Ω.

Refer to specifications for the synchronization
control module, this strobe, and the control panel
to determine allowed wire resistance.

Agency listings

UL 1480. UL 1638 and UL 1971
CAN/, ULC-S541, ULC S526
BS EN 60065:2002 [1]

[1] Nameplate marking is located on the inside surface of the device.