Wiring instructions – Edwards Signaling ANSREM Remote Microphone User Manual

Page 2

Advertising
background image

2 / 2

P/N 3101182 • REV 02 • REB 28FEB13

Wiring instructions

Refer to the wiring, terminal designation, and application

diagrams that follow.
1. Run 3-pair shielded wire (22 AWG minimum) from the ANS

master panel to the ANSREM remote microphone location.

2. Mount the ANSREMSUP supervision card in the ANS

master cabinet, using snap-track.
Attach snap-track to the ANS master cabinet as required. The

supervision card may already be factory-mounted and wired.

3. Make the wiring connections shown in Figure 1.
4. Verify correct installation of the end-of-line resistor (EOLR)

on the ANSREM.
Each module is shipped with an EOLR installed. When the

system has multiple ANSREM units, verify that the EOLR

is installed on the last unit only.

5. Apply power to test the system:

a. Test the ANS master microphone.

b. Test ANSREM remote microphone.

6. Place the panel in alarm and retest the ANS master

microphones:
a. Ensure that the tone and message are broadcast.

b. Test that keying the microphones overrides any

automatic message or tone.

Figure 1: Wiring the ANSREMSUP

(1) All wiring from ANSREMSUP is power-limited. All wiring must be

routed to maintain minimum spacing from any nonpower-limited

wiring.

(2) When circuits are power-limited, use power-limited cable as

detailed in the National Electrical Code, Article 760, such as FPL

or FPLP type cabling.

(3) Battery cabling is nonpower-limited. Do not route any power-

limited wiring within 1/4 in. of the battery cabling.

Figure 2: Wiring the ANSREM

(1) All wiring is power-limited.

(2) The ANSREMSUP must be mounted in the ANS enclosure or in

another UL Listed cabinet within 20 ft. and connected using conduit.

(3) The ANSREMSUP must be mounted using metal standoffs or an

earth ground connection must be made to TB2-7.

(4) Maximum line resistance is 100 Ω per line: approx. 5,000 ft. using

22 AWG. Maximum line resistance also depends on the number

of devices.

2 ANSREMs = 100 ohms max. line resistance

3 ANSREMs = 80 ohms max. line resistance

4 ANSREMs = 65 ohms max. line resistance

5 ANSREMs = 50 ohms max. line resistance

Using more than 5 ANSREMs is not recommended

(5) EOLR is a 6/3 SIP 10 kΩ resistor network. Install EOLR on the

last ANSREM only.

(6) Terminate the cable shielding at the ANSREMSUP. The shielding

must be continuous from the ANSREMSUP to the last ANSREM,

but must not be terminated on any ANSREM card. Join the

shielding at each cable break, but do not land the shielding on the

ANSREM card.

ANS card

ANSREMSUP

card

T

B

3

T

B

2

TO

ANSREM

TO

BATTERIES

(1)

(3)

(2)

ANSREM (2)

ANSREMSUP

V+
NEG
FAULT
PTT
AUDIO

3-pair shielded cabling, 22 AWG minimum (4)

TO

ANS

TB2-11

TB2-10

TB2-6

TB2-2

TB2-1

TB3-8

T

B

2

T

B

3

EOLR (5)

MIC

GAIN

TO ADDITIONAL

ANSREM UNITS

EOLR ON LAST UNIT

ONLY (5)

YEL RED

F

A

U

L

T

I

N

U

S

E

SUPERVISED

UNSUPERVISED

YEL

F

A

U

L

T

TB1

TB1

TB2

1

2

7

6

5

4

3

1

2

3

4

5

1
2
3
4
5

(3)

MICROPHONE

JACK

Shielding (6)

Shielding (6)

(1)