Edwards Signaling ANSZS4B User Manual

Edwards Signaling Safety

Advertising
background image

© 2013 UTC Fire & Security. All rights reserved.

1 / 4

P/N 3101185 • REV 02 • REB 28FEB13

ANSZS2A and ANSZS4B Zone Splitter

Installation Sheet

Product description

The ANSZS2A and ANSZS4B Zone Splitter modules are

intended for use with the ANS25, ANS50, and ANS100 Audio

Notification Systems. Their purpose is to enable the output of

the ANS to be split into multiple zones for paging and alarm

selection.
The modules accept input from the ANS speaker output and

use selectable output relays to distribute the output to the

individual zones. The modules can be cascaded to increase

the number of zones.
The modules provide supervision of the individual zones for

open and short conditions. Indicator LEDs display active or

fault conditions for the individual zones. A fault condition is

reported to the FACP through the same supervisory path as

the ANS25, ANS50, or ANS100.
Zones can be selected manually by switches or through pull-

down inputs. In the event of an alarm condition, the module

defaults to All Call operation. The All Call feature can only be

overridden if the accompanying panel has zone control

features.
Each zone is limited to no more than 25 W and the total

speaker load must not to exceed the output rating of the ANS.

Speaker output can be set to 25 or 70 Vrms, selected by a

jumper position on the ANS25, ANS50, or ANS100.

Operation

In normal standby, the ANSZS2A and ANSZS4B supervise

each speaker zone wire loop. The ANSZS2A provides Style Y

supervision, and the ANSZS4B provides Style Z supervision.
When an open or short fault is detected in a zone, the yellow

LED for that zone turns on. A NC relay contact opens to

present a corresponding fault signal to the FACP providing

supervision of the ANS.
Ground faults in zone circuits are not reported by the

ANSZS2A or ANSZS4B, but are detected and reported by the

ANS25, ANS50, or ANS100.
To manually select a zone, the operator turns on the

corresponding zone switch. The red LED for the switch lights,

and output relay activation is enabled. On activation of the PTT

signal from the ANS the output relay connects the zone to the

ANS speaker output. While the zone is selected, supervision is

suspended.

Caution:

Do not leave a zone switch turned on when

unattended, as this leaves the zone unsupervised.

In an alarm state, the ANSZS2A and ANSZS4B default to All

Call operation. On activation of the ANS “Alarm voltage”

output, all zones are automatically selected, and receive the

EVAC tone and message. Modules have a field-selectable

option for alarm zone activation only if the FACP has the ability

to provide separate pull-down inputs.
If a zone has a short fault, a PTC thermistor for the zone

opens, excluding the zone from output and allowing the other

zones to continue operation. Once the short is removed, the

speaker line must be disconnected for 30 seconds to reset the

PTC.

Specifications

Voltage: 24 Vdc
Current

Standby: 45 mA

Active (All Call): 130 mA

Aux. trouble relay (TB2-7, -8, and -9)

Contact rating: 1 A at 30 Vdc (resistive load)

Connections: Restricted to Class II or power-limited

sources. Interconnected equipment is unsupervised so it

must be in the same room and mounted within 20 feet of

the module.

Speaker circuit EOL: 10 kΩ

Advertising
This manual is related to the following products: