Edwards Signaling E-IDC1A User Manual

Operation, Installation

Advertising
background image

© 2013 UTC Fire & Security. All rights reserved.

1 / 4

P/N 3101191 • REV 02 • REB 25JAN13

E-IDC1A Analog Class A Single Input Module
Installation Sheet

Operation

The module is an analog addressable device used to connect
a normally open, alarm, supervisory, or monitor type dry
contact initiating device circuit (IDC) to a control panel. This
module is designed for Class A circuit operation.

The device address is set using the two rotary switches located
on the front of the module. One device address is required.

The device can be preset for alarm or supervisory operation
using the slide switch located on the front of the module. The
module can also be configured for other device types through
front panel programming or the configuration utility.

Slide switch operation

The following slide switch settings determine the operation of
the module. Setting the initial slide switch position is generally
performed during module installation. This setting can be
changed while the system is operating, but the change must be
confirmed through front panel programming.

Table 1: Slide switch settings

Setting

Operation

Device type description

1

Alarm

Alarm latching: Configures the module for
normally open dry contact initiating
devices. When the NO input contact of
an initiating device is closed, an alarm
signal is sent to the control panel and the
alarm condition is latched at the module.
(Factory default)

2

Not used

3

Supervisory

Supervisory nonlatching US marketplace

Supervisory latching Canadian
marketplace

Nonlatching: Configures the module for
normally open dry contact initiating
devices. When the NO input contact of
an initiating device is closed, a
supervisory signal is sent to the control
panel and the supervisory condition is not
latched at the module.

Latching: Configures the module for
normally open dry contact initiating
devices. When the NO input contact of
an initiating device is closed, a
supervisory signal is sent to the control
panel and the supervisory condition is
latched at the module.

Note: Additional device types are available through front panel
programming or the configuration utility. Refer to applicable control
panel technical reference manual.

Figure 1 : Slide switch

LED operation

The module provides a bicolor LED that shows its status.

Normal: Green LED flashes

Alarm/active: Red LED flashes

Installation

WARNINGS

This module will not operate without electrical power. As

fires frequently cause power interruption, you should

discuss further safeguards with your local fire protection

specialist.

This module does not support conventional smoke

detectors.

Note:

The module is shipped from the factory as an assembled

unit; it contains no user-serviceable parts and should not be
disassembled.

To install the module:

1. Verify that all field wiring is free of opens, shorts, and

ground faults.

2. Make all wiring connections shown in “Wiring.”

3. Set the module address as follows:

Use a screwdriver to adjust the two rotary switches on the
front of the module. Set the TENS rotary switch (0 through
12) for the 10s and 100s digit and the ONES rotary switch
for the 0 through 9 digit. For example: device address 21,
set TENS rotary switch to 2 and set the ONES rotary
switch to 1.

Advertising