Specifications, Regulatory information, Contact information – Edwards Signaling E-RLY User Manual

Page 4

Advertising
background image

4 / 4

P/N 3101196 • REV 02 • ISS 28JAN13

Specifications

Communication line voltage

Maximum 20.6 V peak-to-peak

Current

Standby
Activated


125 µA
125 µA

Contact ratings (pilot duty)

30 VDC
125 VAC


2 A
0.5 A resistive load 60 W or 62.5 VA
max.

Relay type

Form C, programmable

Ground fault impedance

10 kΩ

Compatible electrical boxes

4 inch square, 2-1/2 in. (64 mm)
deep single-gang box
4 inch square, 2-1/2 in. (64 mm)
deep double-gang box
Standard 4 in. square,
1-1/2 in. (38 mm) deep box

Wire size

12, 14, 16, or 18 AWG wire (2.5,
1.5, 1.0, or 0.75 mm

2

) (Sizes 16

and 18 AWG are preferred)

Operating environment

Temperature
Relative humidity


32 to 120°F (0 to 49°C)
0 to 93%, noncondensing

Storage temperature range

–4 to 140°F (–20 to 60°C)

Module address

01 to 64 (64 point control panel)
01 to 127 (127 point control panel)

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture.

North American
standards

CAN/ULC-S527, UL 864

FCC compliance

This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
interference that may cause undesired operation.

Contact information

For contact information, see www.edwardssignaling.com.