Edwards Signaling E-PHD User Manual

Operation, Led operation, Installation

Advertising
background image

© 2013 UTC Fire & Security. All rights reserved.

1 / 4

P/N 3101208 • REV 03 • REB 28JAN13

E-PHD Photoelectric and Fixed Temperature
Heat Detector Installation Sheet

Operation

The E-PHD Photoelectric and Fixed-Temperature Heat
Detector uses an optical sensing chamber to detect smoke and
a fixed-temperature heat sensor to detect heat from fire. The
detector analyzes the sensor data to determine when to initiate
an alarm. The detector continuously monitors changes in
sensitivity due to the environment (e.g., dirt, smoke,
temperature, humidity) and notifies the control panel of its
condition. The heat sensor monitors the temperature of the air
in its surroundings and determines whether an alarm should be
initiated.

The detector is capable of performing comprehensive self-
diagnostics and storing the results. The detector issues a dirty
sensor warning when it reaches its preset limit. This notifies
the operator of the need for service while the detector is still
operating.

LED operation

The detector provides a bicolor LED that shows its status.

Normal: Green LED flashes

Alarm/active: Red LED flashes

Installation

Refer to Edwards Signaling Smoke and Heat Detectors
Applications Bulletin
(P/N 3101212) for additional information
on detector placement and spacing.

WARNINGS

This detector does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.

This detector does not sense fires in areas where smoke
cannot reach the detector. Smoke from fires in walls,
roofs, or on the opposite side of closed doors may not
reach the detector.

Photoelectric detectors have a wide range of sensing
capabilities, but are best suited for detecting slow,
smoldering fires.

To ensure proper operation, schedule maintenance
(regular or selected) in accordance with the requirements
of the authority having jurisdiction. Refer to NFPA 72 and
CAN/ULC−S536.

To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to
room temperature before applying power.

Keep the dust cover (supplied) on the detector during
installation and remove it prior to commissioning and
service. The dust cover is not a substitute for removing the
detector during new construction or heavy remodeling.

To install the detector:

1. Install and wire the detector base using the installation

sheet supplied with the detector base.

2. Set the detector address. Refer to the panel technical

reference manual for a list of valid addresses. Use a
screwdriver to adjust the two rotary switches on the back
of the detector. Set the left rotary switch (0 through 12) for
the 10s and 100s digit and the right rotary switch for the 0
through 9 digit.

3. Connect the detector to the base by rotating the detector

clockwise until it snaps into the locked position.

The head can be removed by turning it counterclockwise.

4. If the head must lock to the base, break away the locking

tab using a pair of pliers.

To then remove the detector head after breaking away the
locking tab, insert a small screwdriver into the slot on the
side of the base and press in while simultaneously turning
the detector head counterclockwise.

Figure 1 : Setting detector address (address 32 shown)

0

1

2

3

4

5 6

12

11

10

9

8

7

0 9

1

2

3

4 5

6

7

8

1

1.

Insert screwdriver here

Advertising