Maintenance, Specifications – Edwards Signaling Genesis WG4 High-Candela Speaker-Strobe User Manual

Page 3

Advertising
background image

P/N 3101853 • REV 2.0 • ISS 21MAR11

3 / 4

Maintenance

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

Caution:

Do not change the factory-applied finish.

Specifications


Operating voltage
Speaker
Default
Strobe


25 VRMS or 70 VRMS, switch selectable
70 VRMS
24 VDC, 24 VFWR nominal

Supervisory voltage

30 V max.

Sound level output

See Table 4

Speaker response

400 to 4,000 Hz

Strobe operating current See Table 8

Light output

Table 5, Table 6, and Figure 6

Wire size

12 to 18 AWG (0.75 to 2.50 mm²)

Compatible electrical
box
Wet
Dry



Model 449
4 in. square by 1-1/2 in. deep box

Operating environment
Temperature
Relative

humidity

Wet
−31 to 151°F (−35 to 66°C)
0 to 95% noncondensing

Table 3: Compatible synchronization sources models

Name Number

Auto-Sync Output
Module

SIGA-CC1S
GSA-MCC1S

GSA-CC1S
SIGA-CC2A

SIGA-MCC1S
SIGA-MCC2A

Genesis Signal
Master Remote
Mount

ADTG1M-RM
MG1M-RM

G1M-RM EG1M-RM

Table 4: Sound level output (dBA)

Wattage

Setting

25 V

70 V

2 W

T

90.0

89.7

1 W

X

87.1

86.9

1/2 W

Y

84.0

83.9

1/4 W

Z

80.8

80.8

dBA = Decibels, A-weighted.

UL 1480: Sound level output at 10 ft. (3.05 m) measured in a
reverberant room using 400 to 4,000 Hz band-limited pink noise.

Table 5: Indoor strobe output (cd)

Lens

Standard

D C B A

Clear UL

1971 102 123 147 161

Amber

UL

1638 84 101 125 130

Figure 5: Wiring, JP1, and switch locations

STROBE +

STROBE +

SPKR +

SPKR +

STROBE -

STROBE -

SPKR -

SPKR -

2

3

1

4

Detail A

5

1. Wire

slot.

2.

S1 wattage-setting switch (see Table 4).

3.

S2 candela-setting switch (see Table 5).

Note: Polarity shown in alarm condition

4.

JP1 strobe temporal mode selection jumper.

5.

S3 speaker voltage-setting switch. UP position is 70 V (default);
DOWN position is 25 V.

Advertising