Genesis Low Frequency (520 Hz) Horn-Strobe

Installation Sheet

Description

The Genesis Low Frequency (520 Hz) Horn-Strobe can be

used for applications where a low frequency alarm notification

appliance with strobe light output is required. The device is

designed for wall mounting and indoor use only. See Table 1

for a list of model numbers.
When this device is used as a low frequency sounder in

sleeping quarters, the strobe's candela switch (Figure 1) must

be set to 110 cd.
The horn-strobe includes field-configurable jumper options for

selecting:

Temporal or steady horn output

Low dB or high dB output

Temporal or continuous pattern strobe

The horn-strobe also includes a field-configurable switch for

setting the strobe candela level. This setting is locked in place

and is visible after final installation.

Table 1: Models
Description

Number

Low frequency (520 Hz) horn, white housing,

no FIRE marking, standard output clear strobe

light

G4LFWN-HVM

Low frequency (520 Hz) horn, white housing,

with FIRE marking, standard output clear

strobe light

G4LFWF-HVM

Low frequency (520 Hz) horn, red housing, no

FIRE marking, standard output clear strobe

light

G4LFRN-HVM

Low frequency (520 Hz) horn, red housing,

with FIRE marking, standard output clear

strobe light

G4LFRF-HVM

Surface wall mount box, white housing

G4B

Surface wall mount box, red housing

G4RB

This strobe features an enhanced synchronization circuit to

comply with the latest requirements of UL 1971. Synchronized

operation requires a separately installed synchronization

device. See the control panel or power supply compatibility list

for compatible synchronization devices.

Installation

Install and wire this device in accordance with applicable

national and local codes, ordinances, and regulations.
The horn-strobe should be mounted so that the entire lens is

not less than 80 in. (2.03 m) and not greater than 96 in.

(2.44 m) above the finished floor. The entire lens should also

be 24 in. (61 cm) or more from the finished ceiling.

WARNING:

Electrocution hazard. To avoid personal injury or

death from electrocution, remove all sources of power and

allow stored energy to discharge before installing or removing

equipment.

Note:

Electrical supervision requires that you break the wire

run at each terminal. Do not loop wires around the terminals.