ESL 511/518 Series
Smoke Detector

Installation Instructions

Description

The ESL 511/518 Series Smoke Detector is a two-wire

detector designed for use with a 24VDC fire system.
Refer to ESL’s Compatibility Index for a complete listing

of compatible control panels. For a copy of the

Compatibility Index, call 1-800-648-7424.

It is important that you read, understand, and follow

the instructions in this guide. If you have questions,

call Sentrol at 1-800-648-7424.
This document is intended for licensed electricians/

alarm installers. Sentrol cannot provide technical

support to unqualified persons.
Failure to properly install, test, and maintain a

smoke detector system may cause it to fail resulting

in loss of life and/or property.

WARNING

!

The detector provides the following features:
Detector/base lock discourages unauthorized removal of

the detector by requiring a screwdriver to remove the

detector from the base.
Mounting base mounts directly to standard single-gang, 3-

inch round or 4-inch octagonal electrical boxes. Can also

be mounted directly to walls and ceilings if the local

authority having jurisdiction allows.

Selecting a Location

Selecting a suitable location is critical to the operation of

smoke detectors. This equipment should be installed in

accordance with the National Fire Protection Association’s

(NFPA) Standard 72.

Important: Regulations pertaining to detector installation

vary from state to state. For more information, contact

your local fire department or local authority having juris-

diction.

In addition to NFPA 72, use the following location guide-

lines to optimize performance and reduce the chance of

false alarms from the detector:
• Locate ceiling-mounted smoke detectors in the center of

a room or hallway at least 4 inches from any walls or

partitions.

• Locate wall-mounted smoke detectors so the top of the

detector is 4 to 12 inches below the ceiling.

• DO NOT locate detectors in or near bathrooms or

kitchens.

• Locate in a suitable environment as follows:

-

Temperature between 32°F (0°C) and 100°F (37.8°C)

- Humidity between 0 and 95% non-condensing

• Locate away from air conditioners, heating registers and

any other ventilation source that may interfere with

smoke entering the detector.

• Mount smoke detectors on a firm permanent surface.

Installing the Detector

All wiring must conform to the National Electric Code

(NEC) and/or local codes having jurisdiction. Use 12 to

24 AWG wire to install the detector.
1. If you are using the detector/base lock, remove the

detector knockout and break off the tab on the mounting

base. See Figure 1.

2. Remove the red plastic dust cover from the detector.

The detector is shipped with a dust cover for protection

on construction sites with dusty environments.

3. Run system wiring to the detector location and mount

electrical boxes if necessary.

4. Line up and attach the gasket and mounting base to the

electrical box, wall, or ceiling using the screws pro-

vided. Use the wall anchors if necessary. See Figure 2.

5. Strip the system wires and connect them to the appropri-

ate terminals on the detector. See Figure 3.

U

L

LISTED

Figure 1 - Detector/Base Lock Knockouts