Edwards Signaling 870 Series Indoor User Manual

Installation instructions for indoor adaptahorns

Advertising
background image

Description

The AdaptaHorns are UL listed vibrating horns. They are low
current, high decibel horns designed for heavy-duty use indoors.
The horns are intended for general signaling applications.

PLC Compatibility

The electrical input load requirements for PLC compatible sig-
naling devices are listed in Table 1. Signaling devices may be
directly connected to output cards that meet these input load re-
quirements.

24V DC electromechanical horns such as the 871-G1, 873-G1,
873DPO-G1 and 875-G1 can produce transient spikes and should
only be used on PLC output cards that have inherent transient
spike suppression. The Process Control Engineer should consult
the PLC manufacturer when connecting 24V DC electromechani-
cal devices to PLCs.

Installation

Flush Mounting (870 and 871 Series)

1.

Using approved wiring methods, connect black wire leads to
power source wires. Polarity is not important.

2.

Ground to wiring system.

3.

Insert horn connector into connector receptacle and secure
horn to backbox with (4) oval head screws (supplied).

Surface Mounting (872, 872DPO, 873, 873DPO, 874, and 875
Series)

1.

Loosen screw at bottom of horn and remove backplate.

2.

Mount plate using one of the following methods:

a.

Mount on any outlet box cover having single gang
opening using #6 screws (supplied).

b.

Mount on a 3 1/4" (83mm), 3 1/2" (89mm), 4" (102mm)
octagon or 4" (102mm) square box using #8 screws
supplied with backbox.

c.

Mount on the wall, for open wiring, using #8 wood screws
(supplied).

3.

Using approved wiring methods connect one wire to each
terminal in backplate. Ground to wiring system.

4.

Place the horn on the mounting plate so that the tab at the top
seats in slot on horn. Press horn firmly against plate and
tighten screw at bottom of unit. See Figure 1.

Installation Instructions for

Indoor AdaptaHorns

P-047550-1894 ISSUE 1 © 1999

CHESHIRE, CT 203-699-3000 FAX 860-677-7746

Table 1. PLC Compatibility

Operating

Maximum off state

Continuous on

Surge (inrush/duration)

Cat. No.

voltage*

leakage current (mA)

current (mA)

(A/ms**)

870-N5

120V AC

25

120

1.02/0.000026

871-G1

24V DC

25

150

1.7/0.000042

872-N5

120V AC

25

120

1.02/0.000026

872DPO-N5

120V AC

25

120

1.02/0.000026

873-G1

24V DC

25

150

1.7/0.000042

873DPO-G1

24V DC

25

150

1.7/0.000042

874-N5

120V AC

25

120

1.02/0.000026

875-G1

24V DC

25

150

1.7/0.000042

*All AC volts at 60 Hz
**Amps/milliseconds

Figure 1. Mounting the Horn on the AdaptaPlate