Edwards Signaling 105 Series User Manual

Warning, Description, Installation

Advertising
background image

Installation Instructions for Cat. 105 Series

Adverse Location Visual Signals

Description

The 105 Series visual signals are heavy duty, reliable, UL,

cUL (General Utility) and CSFM listed (misc. device/control

unit accessory) beacons which, when assembled in accor-

dance with installation instructions, constitute a UL listed

Type 4X enclosure and are UL Listed for Marine Use. They

are designed for use in industrial applications or in appli-

3. Install the mounting attachment as follows:

a. Cat. No. 105BX: Screw the outlet box attachment

to the mounting surface using two screws (not

supplied). suitable for the surface. Attach the

adhesive backed gasket to the top of the 105BX

mounting box, being careful to line up the holes

in the gasket with the mounting holes in the outlet

box.

b. Cat. No. 105BM: Using the four supplied screws,

secure the mounting bracket to Cat. No. 105BX

outlet box attachment as shown in Figure 1. Attach

the adhesive backed gasket to the top of the 105BM

mounting bracket, being careful to line up the

holes in the gasket with the mounting holes in

the outlet box.

c. Cat. No. 105PM: Install 3/4" (19 mm) conduit.

Screw the pipe mount attachment onto the 3/4"

(19 mm) conduit. Attach the adhesive backed

gasket to the top of the 105PM pipe mount

attachment, being careful to line up the holes in

WARNING

To prevent electrical shock, do not connect power
until instructed to do so.

Installation must be in accordance with local codes. The

lens should be positioned up for outdoor applications.
1. Select a mounting configuration (Figure 6).
NOTE: When mounting using the Cat. No. 105BM

mounting bracket, the Cat. No. 105BX outlet

box attachment must also be used as shown in

Figure 1.

2. Pull field wiring into the mounting attachment.

WARNING

The 105BX junction box, 105BM mounting bracket
and 105PM pipe mount attachments can be used with
metallic wiring systems only when installed at the
end of a run.

Table 1. Hazardous Location Ratings

Cat. No.

Class

Division

Group

Operating Temperature

105FINH*-G1

I

2

A, B, C, D

T2D (215C, 419F)

105SINH*-G1

I I

2

F, G

T4A (120C, 248F)

105FINH*-G5

I I I

T4A (120C, 248F)

105SINH*-G5
105FINH*-N5

I

2

A, B, C, D

T2 (300C, 572F)

105SINH*-N5

I I

2

F, G

T4 (135C, 275F)

I I I

T4 (135C, 275F)

105HIST*-N5

I

2

A, B, C, D

T2 (300C, 572F)

105HIST*-R5

I I

2

F, G

T3B (165C, 329F)

I I I

T3B (165C, 329F)

105HIST*-EK

I

2

A, B, C, D

T2A (280C, 536F)

I I

2

F, G

T3B (165C, 329F)

I I I

T3B (165C, 329F)

105ST*-G1

I

2

A, B, C, D

T3 (200C, 392F)

105ST*-N5

I I

2

F, G

T4A (120C, 248F)

105ST*-R5

I I I

T4A (120C, 248F)

105FLED*-N5

I

2

A, B, C, D

T5 (100C, 212F)

105SLED*-N5

I I

2

F, G

T5 (100C, 212F)

105FLED*-G1

I I I

T5 (100C, 212F)

105SLED*-G1

Installation

cations where a Type 4X enclosure is required. The units

are available in steady-on halogen or LED, flashing halo-

gen or LED, 3 Joule strobe or 8 Joule high intensity strobe.

When assembled in accordance with these instructions,

the 105 Series visual signals are UL Listed for use in Haz-

ardous Locations with Operating Temperatures listed in

Table 1.
For specification details, see Table 2.

P/N 3100290 ISSUE 3 © 2002

CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH SERV.)

WARNING

The 105BX junction box, 105BM mounting bracket
and 105PM pipe mount attachments are non-conduc-
tive plastic fixtures and do not provide earth-ground
continuity when attached to metallic wiring systems.
Therefore, they are intended for use with the 105
series visual signals only when earth-grounding is
not required.

Advertising