P/N 3100101 ISSUE 6

Figure 2. Detail of Ceiling Mounting

Figure 3. Detail of Bracket Mounting

Figure 4. Wiring Diagram

NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device for constant input voltage. Do not connect to “coded” or pulsating voltage.

From Power Source

or

Previous Signaling Device

End-of-Line Resistor,
when required with
supervised system

KEY:

Light symbol -

Wire nut symbol -

(+)

Red

(+)

Red

(+)

Red

(+)

Red

Black

(-)

Black

(-)

Black

(-)

Black

(-)

Series

106DEX

Series

106DEX

(+)

(-)

NOTE:

For non-fire alarm use without field wire supervision installer can tie the two red leads together and

tie the two black leads together.

For strobe tube replacement, disconnect from the supply

circuit and allow five (5) minutes for stored energy to dis-

sipate before starting work or disassembly (Figure 6).
1. Loosen the (3) guard screws and remove the guard.
2. Loosen the globe and ring assembly set screw. Insert

a suitable tool into the notches in the globe and ring

assembly and loosen the assembly by prying in a

counterclockwise direction. Remove the ring and

globe assembly.

Maintenance

Maintenance

Maintenance

Maintenance

Maintenance

CAUTION

When replacing the strobe tube, do not handle the
tube. Hold the strobe tube only by its base to pre-
vent damage to the tube.

3. Refer to Table 2 for the correct replacement catalog

number and replace the necessary part.

4. To replace, simply screw the unit on until it seats firmly

onto its gasket. Tighten the unit another 1/8 to 1/4

turn. Tighten the setscrew.

5. Reinstall the guard, where applicable, and secure using

the three supplied screws.

6. After the unit is assembled, apply power and make

sure the unit functions properly.

WARNING

To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.

To reduce the risk of ignition of hazardous atmo-
spheres and shock, disconnect from the supply and
circuit and allow five (5) minutes for stored energy to
dissipate before disassembling the unit.

13.88"

(352.6 mm)

12.38"

(314.45mm)

13.75"

(349.25mm)

7.80"

(198.12mm)

4.93"

(125.2mm)

5.95"

(151.13mm)

13.0"

(330.2mm)

13.38"

(339.85mm)

7.80"

(198.12mm)