Maintenance

WARNINGS

To prevent electrical shock, ensure that power is
disconnected before installing the signal.

To prevent leakage and potential electrical shock, use
care when disassembling the signal to prevent tearing of
the permanently affixed gaskets provided for
weatherproofing.

Horn replacement

Refer to Table 2 for the required horn. After disconnecting
power, remove the old horn and attach the new one. Reattach
the horn module wiring to the flasher module wiring.

Cleaning

Caution:

To prevent damage to the lens, do not use abrasive

materials or cleaners.

The signal lens should be cleaned periodically to maintain
optimum light visibility. It can be cleaned with a soft cloth or
sponge using mild detergent. Dry the lens completely before
replacing it.

Table 2: Replacement parts

Catalog Number

51XBRF*120A

51XBRF*24D

Replacement horn

123A-N5

118-G1

Replacement lens

92-L*

92-L*

Solid state flasher module P-041917-0026

P-041917-0028

*Letter in this position designates lens and LED color = A = amber, B =
blue, W = white, G = green, R = red

Troubleshooting

If the LED is flashing and the horn is not buzzing then the solid
state flasher needs to be replaced. If after the replacement of
solid state flasher the horn is still not buzzing, then the horn
needs to be replaced. If the LED is not flashing and the horn is
buzzing, then the LED circuit is damaged (the LED circuit is not
offered as replacement part).

Specifications

Catalog number

Electrical specs

Color

51XBRFA120A

120 VAC, 0.175 A

Amber

51XBRFB120A

120 VAC, 0.175 A

Blue

51XBRFG120A

120 VAC, 0.175 A

Green

51XBRFR120A

120 VAC, 0.175 A

Red

51XBRFW120A

120 VAC, 0.175 A

White

51XBRFA24D

24 VDC, 0.275 A

Amber

51XBRFB24D

24 VDC, 0.275 A

Blue

51XBRFG24D

24 VDC, 0.275 A

Green

51XBRFR24D

24 VDC, 0.275 A

Red

51XBRFW24D

24 VDC, 0.275 A

White

Regulatory information


Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

North American
standards

UL 1638

Contact information

For contact information see our Web site:
www.edwardssignaling.com