Edwards Signaling 5521 User Manual

Page 2

Advertising
background image

P/N P-047550-0437 ISSUE 2

b. Mounting to electrical box:

Bring wires installed in step 4 through center hole

of mounting plate.
Align appropriate holes in mounting plate with

mounting screw holes in electrical box. Fasten

plate to single gang box using the two #6-32 x 5/

8" (16 mm) screws supplied with the signal, or

fasten to octagon or square box using screws

supplied with the box.

c. Weatherproof installation:

Fasten the Cat. No. 349 Weatherproof Box to the

mounting surface by installing the three

#8 x 1 1/4" (32 mm) wood screws and three fiber

washers, supplied with the box, through the

mounting holes in the rear of the box.
Bring wires installed in step 4 through 3/4" (19

mm)-14 NPT conduit and through conduit entrance

hole into box. Secure conduit to box.
Align appropriate holes in mounting plate with

mounting screw holes in bosses of box and fasten

plate to box using the four #8-32 x 7/16" (11 mm)

machine screws supplied with the box.

5. Connect wires from power source or transformer to

the terminals of the plug receptacle on the mounting

plate as shown in Figure 3.

6. Hook signal on mounting plate by engaging hanger

on plate into slot in top of signal housing (Figure 3).

Press signal flush to mounting plate to mate plug in

rear of signal housing with plug receptacle on

mounting plate. Tighten screw, loosened in step 1, to

secure signal to plate.

For Cat. No. 5521-S1, install as follows:
1. Loosen the screw at the bottom of the signal housing

and remove the mounting plate from the signal (Figure

2).

2. Fasten the Cat. No. 349-R Weatherproof Box to the

mounting surface by installing the three #8 x 1 1/4"

(32 mm) wood screws and three fiber washers, supplied

with the box, through the mounting holes in the rear

of the box.

3. Bring 250V DC power source wires through 3/4" (19

mm)-14 NPT conduit and through conduit entrance

hole into box. Secure conduit to box.

4. Place resistor bracket assembly P-039964-0424 in box

with resistor facing rear of box as shown in Figure 5.

Connect the 250V power source wires to the terminals

on the assembly (Figure 4).

5. Bring the two wire leads from the resistor bracket

assembly through the center hole in the mounting

plate. Align holes in bracket with mounting screw

holes in lower bosses of box when upper conduit

entrance hole is used (Figure 5). When bottom conduit

entrance hole is used, bracket must be aligned with

screw holes in upper bosses in box.

6. Align appropriate holes in mounting plate with

mounting screw holes in bosses of box, and fasten

plate and resistor bracket assembly to box using the

four #8-32 x 7/16" (11 mm) machine screws supplied

with box.

7. Connect wire leads from resistor bracket assembly to

the terminals of the plug receptacle on the mounting

plate (Figure 3).

8. Hook signal on mounting plate by engaging hanger

on plate into slot in top of signal housing. Press signal

flush to mounting plate to mate plug in rear of signal

housing with plug receptacle on mounting plate.

Tighten screw loosened in step 1 to secure signal to

plate.

Adjusting Speaker Direction

To adjust the speaker direction, loosen the nut shown in

Figure 2. Rotate the speaker to the desired position and

tighten the nut. The speaker position can be adjusted

within a 90° range vertically and 180° range horizontally.

Operational Test

Apply power to the signal and verify that it sounds. For

models with horn/siren mode selection, verify that selected

type of signal is sounding.

Maintenance and Subsequent Testing

Examine the signal annually for accumulation of dirt.

Clean if necessary.
Test the signal semi-annually or at the intervals required

by applicable regulations and codes.

Figure 2. Mounting Plate Removal and

Speaker Directional Adjustment

Advertising
This manual is related to the following products: