Edwards Signaling 6536-G5 User Manual

Warning, Description, Installation

Advertising
background image

P-047550-1872 ISSUE 1 © 1999

CHESHIRE, CT 203-699-3300 FAX 860-677-7746

Installation Instructions for the

6536-G5 Horn/Strobe

Description

The 6536-G5 is an audible/visual signal UL Listed for general
purpose signaling applications.

Installation

A qualified electrician familiar with National Electrical Code
and local code requirements must install this product. Failure to
follow the safety precautions in this instruction sheet could result
in product or property damage, severe personal injury or death.

Figure 1. Details of Horn/Strobe

2.

Connect the horn/strobe wire leads and terminals (Figure 2).
The horn and strobe are connected together at the factory.

NOTE: To connect the horn and strobe to different circuits,

loosen the terminals, remove the two wires and cap off
with wire nuts.

3.

Mount the horn/strobe onto the electrical box. Secure it using
two screws (supplied).

4.

Perform an operational test.

Maintenance

WARNING

To reduce the risk of shock, do not remove lens or
tamper with unit when the circuit is energized. Do
not connect AC power until installation is complete.

WARNING

To reduce the risk of shock, do not remove lens or
tamper with unit when the circuit is energized.
Disconnect power and allow five (5) minutes for
stored energy to dissipate before starting work or
disassembly. High energy could be stored in the
strobe circuit once it is energized.

Figure 2. Connecting the Horn and Strobe

The 6536-G5 horn/strobe (Figure 1) can be mounted on any single
gang 2" x 4" (51 mm x 102 mm) electrical box, double gang 4" x 4"
(102 mm x 102 mm) electrical box, or standard 4" x 4" (102 mm x
102 mm) junction box with a plaster ring.

1.

Install an appropriate electrical box using suitable hardware.

Perform regularly scheduled testing at least twice a year or more
often as dictated by local authorities having jurisdiction.

Table 1. Specifications

Operating Voltage

24V 50/60 Hz

24V DC

Alarm Current

175 mA

125 mA

SIGNAL

STROBE

4 1/2"

(114 mm)

4 9/16"

(116 mm)

Strobe

+

_

To separate 24V AC
or 24V DC power source

Horn

Mounting
screws

FRONT
VIEW

BACK
VIEW

Factory installed
wires

+

-

S

Factory

Connected

Single 24V AC or

24V DC Power Source

Electrical Box

Red (+)

White (-)

Advertising