Wire routing, Wiring diagrams – Edwards Signaling FireShield Single-Zone Panel User Manual

Page 3

Advertising
background image

Installation Sheet

04MAR03

P/N: 3100589 REV: 1.0

FireShield Single-Zone Panel - Installation and Operating Instructions

3 / 6

Wire routing

All wiring is power-limited except for AC power and battery
wiring. All wiring is supervised unless noted otherwise.

Keep power-limited wiring in the shaded

area and nonpower-limited wiring in the
unshaded area at all times.

Wiring diagrams

The following diagrams show field wiring, AC power and
battery wiring, and RTU wiring.

Field wiring

AUX PW

R –

AU

X PW

R +

C

o

m

m

on

t

ro

ubl

e

re

la

y

1

A

@

3

0

Vd

c,

r

es

ist

iv

e

N

ons

upe

rv

is

ed

[7

][9

]

C

o

m

m

o

n

al

ar

m

r

el

ay

1

A

@

30

Vd

c,

r

esi

st

iv

e

N

o

ns

up

er

vi

se

d

[7

][

9]

AUX

PW

R

o

ut

p

ut

24

V

dc,

nom

in

al

@

0

.1

A

EOLR

+

IDC–

IDC+

+

+

NAC–

NAC+

+

EOLR

NOTIFICATION APPLIANCE CIRCUITS [2] [3] [4] [8]

Class B (Style Y)

Operating voltage: 24 Vfwr

Operating current: 1.0 A

EOLR:

Circuit impedance: 13 , 50.0 F, max

4.7 k , 1/2 W (P/N EOL4.7)

µ

INITIATING DEVICE CIRCUITS [2] [3] [6] [8]

Class B (Style B)

Operating voltage: 16.7 to 26.4 Vdc

Operating current: 3.0 mA

Circuit impedance: 13 , 50.0 F, max

EOLR: 4.7 k , 1/2 W (P/N EOL4.7)

µ

AC power and battery wiring

24 Vac

IN

Main supply circuit

120 V, 60 Hz, 0.36 A
from dedicated branch
supply

EGND

Li

n

e

Ea

rt

h G

N

D

Ne

u

tr

a

l

Red

Black

Rechargeable battery circuit

Voltage: 24 Vdc

Amp-hour capacity: 4.5 Ah max.

sealed lead acid batteries only

12 Vdc
Battery

12 Vdc
Battery

Note: Make sure to
reattach the AC

terminal cover when
power wiring is
complete.

RTU wiring

Jumper wire

TB1

+

+

NC NO

RTU

[9]

NO

ALARM

NC

NO

NC

+

AUX PWR

TROUBLE

Notes

The following notes match the wiring label notes inside the panel,
and are not numbered sequentially.

[2] Class B wiring only

[3] Listed EOLRs must be installed as shown for proper

supervision

[4] Marking indicates output signal polarity when the circuit is

active. Polarity reverses when the circuit is not active. Wire
notification appliances accordingly. Notification appliance
polarity shown in active state.

[6] When the IDC is programmed for alarm verification, both

automatic and manually activated alarm initiating devices can
be connected simultaneously. Manually initiated devices will
not be verified (delayed).

[7] Relay circuits can only be connected to power-limited sources

[8] Installation limits under jurisdiction of local authority

[9] Contacts shown in normal condition