   Figure 1 illustrates how to connect two 100 AH batteries to the charger:

Figure 1 Connecting Two 100 Amp Hour Batteries to a Charger

Table 1 contains instructions for connecting two batteries to the charger:

Step Action

1

Remove all power sources to the charger.

2

Connect the battery negative cable to the TB2 terminal (on the charger labeled
“Battery –”) as shown in Figure 1.

3

Connect the battery positive cable to the TB2 terminal (on the charger labeled
“Battery +”) as shown in Figure 1.

4

Proceed to the section titled “Connecting the Charger” in the CHG-120 Series
Instruction Manual. Do not connect the Battery Interconnect Cable at this
time
—refer to the section titled “Starting the Charger” in the CHG-120 Series
Instruction Manual.

Table 1 Connecting 100 AH Batteries

Connecting the CHG-120 Series Battery Charger for Additional Current
A maximum of 10 amps is available from each charger output. To draw additional current from the charger, a load
can be connected directly to the batteries as illustrated in Figure 1.