Fire-Lite MDF-300 Dual Monitor Module User Manual

Page 2

Advertising
background image

Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:

A78-2280-38

F300-09-00

2

I56-0013-01R

©2000 Fire•Lite Alarms, Inc.

0

7 8

6

5

4
3

2

1

9

10

11

12

13

14

15

FROM PANEL OR

(+)

(—

)

TO NEXT

(+)

(—

)

DEVICE

(+)

(—

)

MONITOR

CONNECT MODULES TO LISTED COMPATIBLE

32 VDC MAX.

SHIELDED-TWISTED PAIR

IS RECOMMENDED

CONTROL PANELS ONLY

PREVIOUS DEVICE

COMMUNICATION LINE

MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9)
RESPONDS AT NEXT HIGHER ADDRESS.

ANY NUMBER OF UL LISTED CONTACT CLOSURE

DEVICES MAY BE USED. DO NOT MIX FIRE ALARM

INITIATING, SUPERVISORY, OR SECURITY DEVICES

ON THE SAME INITIATING DEVICE CIRCUIT.

INSTALL CONTACT CLOSURE DEVICES PER

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

47 K EOL
RESISTOR
ELR-47K

MODULE

47 K EOL
RESISTOR
ELR-47K

H

L

9

8

7

6

5

4

3

2

1

0

TENS

ONES

ADDRESS

LOOP

0

2

4

6

8

TWO INITIATING DEVICE CIRCUITS (L & H),

EACH POWER LIMITED TO 230 A @ 12VDC MAX.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED