Technical specifications – HT instruments HT78 User Manual

Page 14

Advertising
background image

HT78

EN - 13

6. TECHNICAL SPECIFICATIONS

6.1. CHARACTERISTICS
Accuracy is indicated as [% rdg + (number of dgt) * resolution] referred to: 23°C(73°F) ±
5°C(41°F); RH< 80%

AC TRMS Current

Range Resolution

Accuracy

Bandwidht

Max input current

300mA 0.1mA

3Arms

3A 0.001A

30Arms

30A 0.01A

300Arms

300A 0.1A

±(1.5%rdg+ 8dgt)

3000A 1A

±(2.0%rdg+ 8dgt)

50

÷60Hz

3000Arms


DC analogical output

Range Resolution

Accuracy

Bandwidht

Max input current

300mA 1mV/1mA

3Arms

3A 1mV/0.01A

30Arms

30A 1mV/0.1A

300Arms

300A 1mV/1A

3000A 1mV/10A

±(1.5% FS)

50

÷60Hz

3000Arms

FS = full scale of any range

Internal filter

Type of filter

Cut-off frequency

Low-pass 150Hz

6.1.1. Safety
Comply with:

IEC/EN61010-1, IEC/EN61010-2-032

Insulation: double

insulation

Pollution degree:

2

Max height:

2000m (6562 ft)

Installation category:

CAT II 600V, CAT III 300V to the ground


6.1.2. General data
Mechanical characteristics
Size:

341(L) x 194(W) x 52(H)mm ; 13(L) x 8(W) x 2(H) inch

Weight (including batteries): 1.9kg (67 ounces)
Max conductor size:

108mm (4”)


Supply
Batteries type:

2x1.5V alkaline batteries type AAA LR03

Low battery indication:

” symbol is displayed when the level is low

Battery life:

approx 200 hours of continuous use

AutoPowerOFF:

approx 10 minutes of idleness


Display
Characteristics:

4 LCD 3200 points plus decimal point, sign and bargraph

Sample rate:

2 times/sec

Conversion mode:

TRMS

Over range symbol:

“O.L” indication at display

Advertising