KEPCO HSF 1500W Series (all models) Quick Start Guides User Manual

Kepco, Single output 3u hot swap plug-in power supplies, I — introduction

Advertising
background image

©2013, KEPCO, INC

1

Data subject to change without notice

228-1704 REV 1

KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11355 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102

http://www.kepcopower.com " email: [email protected]

Q U I C K S T A R T G U I D E

KEPCO

An ISO 9001 Company.

HSF

1200W/1500W

SINGLE OUTPUT 3U

HOT SWAP PLUG-IN POWER SUPPLIES

I — INTRODUCTION

SCOPE OF MANUAL. This Quick Start Guide covers

the installation and operation of the Kepco HSF 1200W/
1500W Series of Hot Swap Plug-in Power Supplies. Full
specifications are listed in the HSF 1200W/1500W Opera-
tor Manual that can be downloaded from the Kepco web
site at:
www.kepcopower.com/support/opmanls.htm#hsf

These power supplies are designed to be installed in
Kepco’s RA 19-4C Rack Adapter. The RA 19-4C Operator
Manual can be downloaded from the Kepco web site at:
www.kepcopower.com/support/opmanls.htm#ra19-4c

FACTORY DEFAULTS. This guide covers only units as

shipped from the factory with the two internal DIP switches
set to default configuration (see Figure 1). For other config-
urations, refer to applicable Operator Manual.

DESCRIPTION. The Kepco HSF 1200W/1500W Series

are hot swappable, high frequency switching, plug-in power
supplies. Models may be selected for outputs of 24V, 36V
or 48V. They employ power factor correction and are
designed to operate in a fault tolerant power system with a
nominal a-c input of 100V a-c to 240V a-c (input voltage
range 85 to 265 Va-c), 50-60 Hz (input frequency range 47-
440Hz). A built-in current balancing circuit and OR-ing
diodes allow configuration for hot-swap and parallel-redun-
dant N+1 operation. All input/output connections are
through a 24-pin connector that plugs in to the rack
adapter. All external connections are made through the
rack adapter’s I/O connector.

OPTIONS. M models include a digital meter which dis-

plays either voltage or current as determined by a front
panel switch. The front panel V or A indicator lights to show
whether voltage (V) or current (A) is displayed. Metered
and non-metered models are completely interchangeable.

FIGURE 1. DIP SWITCH FACTORY DEFAULTS

C Models include a current sense resistor which allows
external current monitoring within 3% (contact Kepco if
greater accuracy is required). RoHS-compliant models
indicated by HSF* (e.g., HSF 24*50M).

II — INSTALLATION

PRIOR TO MOUNTING. Two internal DIP switches are

preconfigured for the factory defaults (see Figure 1). To
change the factory defaults, refer to the operator manual
and configure the DIP switches prior to installation.

KEYING. The units are keyed by voltage at the factory.

Refer to the RA 19-4C Operator Manual to make the rack
adapter slot match the HSF.

MOUNTING THE POWER SUPPLY. Release the two

cap head screw retaining latches (see Figure 2) by loosen-

ing the cap-head screw approximately 1/2 turn CCW (use
5/32" hex key) and slide to the open (up) position. Insert the
power supply in the slot, then retighten the cap-head
screws CW until snug. DO NOT OVERTIGHTEN! To
release, follow the same procedure, except lift the latch to
the top of the slot. Be sure to move the latch completely up
or down to ensure full engagement and disengagement of
the latching mechanism. When the HSF is not installed in
its plug-in rack adapter, it is recommended that the latch be
secured in the open (up) position to prevent damage.

TABLE 1. HSF 1200W/1500W HOT SWAP MODELS

MODELS

24V

36V

48V

HSF 24-50

HSF 36-42

HSF 48-32

NOTE: Options include suffix M, or C: M for meter, C for current monitor.
HSF* indicates RoHS compliance.

3043519

- FRONT PANEL VADJ CONTROL
- RELAY ALARM SELECTED
- VISUAL ALARM DISABLED
- REMOTE ON-OFF DISABLED

Factory default settings

for all options

1
2
3
4

5
6

7
8

8

SW1

SW2

2

5

5

7
8

6

7
8

6

3
4

4

3

5

7

6

4

3

ON

1
2

OFF

1
2

OFF

1

ON

TAB

Advertising
This manual is related to the following products: