KEPCO HSF 600W Series (suffix A and AM) Operator Manuals User Manual

Page 18

Advertising
background image

16

HSF(A) 600W 101013

5. Voltage Set Restrictions. When units are at light load (under 10% of nominal),

and voltage settings are less than 80% of nominal, voltage set restriction are

required. To avoid a “slave idle” condition (PF signal set, red ALARM indicator on)

the output voltage of all parallel-connected units must be set within 0.5% of each

other and be at least 80% of their nominal (rated) output voltage (90% for 48V

model).