KEPCO HSF 100W Series User Manual

Hsf 100w, Kepco, I — introduction

Advertising
background image

©2006, KEPCO, INC

1

Data subject to change without notice

228-1300 REV 5

I N S T R U C T I O N M A N U A L

KEPCO

KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11352 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102

http://www.kepcopower.com " email: [email protected]

An ISO 9001 Company.

HSF

100W

KEPCO SINGLE OUTPUT 100 WATT

HOT SWAP PLUG-IN POWER SUPPLIES

I — INTRODUCTION

The Kepco HSF 100 Watt series hot swappable, high frequency switching, plug-in power supplies employ forward conversion

and are designed to operate in a fault tolerant power system with either a-c or d-c input. A resistor and thyristor soft-start circuit

limits start-up surge. A built-in forced current share circuit and OR-ing diodes allow configuration for hot-swap and parallel-

redundant N+1 operation.

These power supplies are designed to be used with Kepco’s Series RA 19-(X)B rack adapters (Figure 1). The RA 19-8B rack

adapter accepts up to eight 50 Watt or 100 Watt units (see Figure 1); RA 19-7B accepts up to four 50 Watt or 100 Watt units and

three 150 Watt units; RA 19-6B accepts up to six 150 Watt units. All input/output connections are through a 24 pin connector

that plugs in to the rack adapter. All external connections are made through the rack adapter. Surface mount technology permits

efficient component layout for minimum mounting space.

Six models may be selected for outputs of 5, 12, 15, 24, 28, or 48V (see Table 1).

When the input is cut off, the output is maintained for 15 milliseconds minimum. If the power supply shuts down due to an output

overvoltage condition, it is then necessary to wait 90 seconds minimum (120V a-c input) or 120 seconds minimum (240V a-c

input) before turning the unit on again. EMI filtering is designed to meet FCC Class B rating and VDE 0871 Class B rating. This

page contains specifications for each model of the HSF 100 Watt Series. Environmental specifications for each model are the

same.

II — FEATURES

FRONT PANEL ACCESS. The front panel provides a power ON/OFF switch controlling input power and a “VDC ON” light

which indicates when the unit is operating. NOTE: The ON/OFF switch must be set to OFF before removing unit from rack

adapter. The front panel “MASTER ON” LED lights when 1) the unit operates independently, or 2) the unit is used in parallel

redundant configurations while a) the output is less than 10% of nominal or b) the output is within 10% to 100% of nominal and

the unit is functioning as a master. In parallel redundant configurations, the module with the highest voltage functions as the

master. The other units are slaves, and track the output voltage of the master. Refer to Current Share Bus (CSB) on page 3 for

details. The front panel Vadj trimmer provides adjustment of the output voltage within the limits specified in Table 1; test points

connected to the +S and –S lines are available at the front panel for measuring the output.

FORCED CURRENT SHARE CIRCUIT. When units are configured for N+1 parallel redundant operation, it is desirable for cur-

rent to be divided equally among the paralleled supplies. When the CSB (Current Share Bus) lines of paralleled HSF units are

connected together, the load current is forced to divide equally between all paralleled units. If one unit fails, the remaining units

will continue to supply the load, and the load current will be divided equally among the remaining operating units. The failed unit

is automatically isolated from the circuit by a built-in isolation diode. Refer to Current Share Bus (CSB) on page 3 for details.

TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, HSF 100W SERIES

MODEL

HSF 5-20

HSF 12-8.3

HSF 15-6.6

HSF 24-4.2

HSF28-3.5

HSF 48-2

OUTPUT VOLTS, d-c (NOMINAL)

5V

12V

15V

24V

28V

48V

ADJUSTMENT RANGE

4.5 - 5.5V

11.4 - 12.6V

13.5 - 16.5V

22.5 - 25.5V

26.5 - 29.5V

45.0 - 51.0

OUTPUT CURRENT (NOMINAL)

(1)

(1) Derates same as Ouptut Power.

20A

8.3A

6.6A

4.2A

3.5A

2.0A

OUTPUT POWER (NOMINAL)

(2)

(2) See power derating curve, Figure 4.

100W

99.6W

99W

100.8W

98W

96W

RIPPLE

AND

NOISE

(mV p-p)

0-40°C

10-100% LOAD

source (typ)

10

15

15

20

20

20

source (max)

15

30

40

40

40

40

switching (typ)

30

35

40

50

60

80

switching (max)

65

70

80

110

140

220

spike noise (d-c—50MHz)

<120

<190

<220

<310

<330

<530

OVERVOLTAGE SETTING (25 °C, NOM. INPUT)

6.5 - 7.5V

13.7 - 15.7V

17.0 - 19.0V

27.0 - 30.5V

32.0 - 35.0

53.5 - 60.0

OVERCURRENT SETTING (25 °C, NOM. INPUT)

Rectangular type characteristic

21.0 - 24.0A

8.7 - 10.0A

7.0 - 8.0A

4.4 - 5.2A

3.7 - 4.2A

2.1 - 2.4A

Advertising