KEPCO KES 24V User Manual

24 volts, Kepco, 24 volt engine start battery charger

Advertising
background image

I N S T R U C T I O N M A N U A L

KES

KEPCO

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102

www.kepcochargers.com email: [email protected]

An ISO 9001 Company.

24 VOLTS

©2010, KEPCO, INC

1

Data subject to change without notice

228-1593 REV 4

24 VOLT ENGINE START BATTERY CHARGER

I — INTRODUCTION

SCOPE OF MANUAL.

This instruction manual covers the installation and operation of the Kepco Series KES 24 Volt Engine Start Battery Chargers (see

Table 1).

WARNINGS and CAUTIONS

Do not operate the unit without proper grounding. Improper grounding risks an electric shock that could result in

injury or death.

Do not touch the unit’s input or output terminals to avoid the risk of electric shock that could result in injury or death.

Energy stored in the unit’s output capacitor is present on the DC OUTPUT terminals for a few seconds even after the

a-c input voltage is removed.

The Float Voltage and Current Limit must be preset prior to starting the initial charge to avoid damage to the battery

being charged.

To avoid damage to the unit or the battery being charged, never obstruct the ventilation holes at the sides of the unit.

The unit must be installed in a properly ventilated area, free of smoke and corrosive or explosive vapors.

DESCRIPTION.

The Kepco Series KES 24 Volt Engine Start Battery Chargers are wall-mounted units designed to charge 24-Volt lead-acid or nickel

cadmium batteries used in engine start applications. Model KES 24-10 is rated at 10 Amps, Model KES 24-20 is rated at 20 Amps and

Model KES 24-50 is rated at 50 Amps. The output voltage and output current limit are factory set, and are adjustable from the front

panel recessed trimpots (see Table 1 for values). An optional temperature compensation probe (not supplied) provides automatic adjust-

ment of the float voltage to accommodate temperatures from 0° to 35°C. Units may be operated with a nominal 100V a-c to 240V a-c

(input voltage range 85 to 265 Va-c), 50-60 Hz nominal, range 47-66Hz (see Table 1, Note 1). Both AC lines are protected by fuses. A

front panel ammeter shows charging current.

The heart of the KES 24 Volt Series is a solid-state switching power supply, Kepco’s RKW, which has an integral cooling fan (KES 24-50

has two fans). A front panel CHARGER ON indicator lights the unit is on. The front panel TEMP PROBE NOT CONNECTED indicator

lights to show that the temperature compensation probe is not attached to the unit. An internal diode network across the output provides

protection in the event that the battery connections are reversed, causing the front panel circuit breaker to open.

FIGURE 1. 24 VOLT ENGINE START BATTERY CHARGER, FRONT VIEW

O

P

E

N

A

R

M

C

L

O

S

E

D

+

R

C

-R

C

ALARM

REMOTE

CONTROL

GND

L (L1) N (L2)

AC INPUT

DC OUTPUT

NC

-

+

Advertising