DESCRIPTION.

Temperature compensation can prolong battery life by adjusting the float voltage automatically.

The Kepco TEMPCO Model Temperature Compensation Probes allow the output voltage of a Kepco battery charger

to be automatically decreased or increased for temperatures above or below 77°F (25°C), respectively, in the 0°C to

35°C range. Beyond this range, the compensation is clamped to 0°C and 35°C for temperatures below 0°C and

above 35°C, respectively. Compensation is 3mV/(°F)(cell) or 5.4mV/(°C)(cell) for cells of 2.23V nominal, and can be

calculated as follows:

• dV

T

= – (K

T

) (Ta – 77) (V

B

/2.23) where

• V

B

= Battery voltage,

• K

T

= 0.003V/(°F)(cell),

• Ta = ambient temperature in °F

• 2.23 = cell voltage at 77°F.

Thus, for example, to calculate the float voltage V

F

of a 14.5V battery charging at 80°F:

V

F

= V

B

+ dV

T

= 14.5 –(0.003)(80–77)(14.5/2.23)
= 14.5 – 0.059
= 14.441V.

The TEMPCO Models are identified by the length of the cable attached to the probe. TEMPCO-10 is 10 feet long,

TEMPCO-50 is 50 feet long, TEMPCO-100 is 100 feet long and TEMPCO-200 is 200 feet long.

INSTALLATION.

1 Connect the temperature probe cable to the TEMP PROBE connector at the front panel of the Kepco battery

charger. For Kepco KES or KRR battery chargers, verify that the TEMP PROBE NOT CONNECTED indicator on

the battery charger is not lit.

2 Attach the temperature probe to the negative (–) terminal of the battery being charged. If the threaded stud is

long enough, mount the probe on the threaded stud and attach it with another nut. Otherwise, remove the exist-

ing nut and use it to attach the temperature probe. In either case observe torque requirements when tightening

the nut. NOTE: The temperature probe is internally isolated from the battery charger connections, so it may be

connected to the (+) terminal of the battery if desired.