AMX Heavy Duty DC Module RDM-HDC User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-HDC Heavy Duty DC Module

2400 W, 0-12 VDC

The RDM-HDC Heavy Duty DC Module is a heavy-duty 2400 W module for
dimming of fluorescent ballast loads. It uses a 0 to 12 VDC current sinking
or sourcing for use with all four-wire ballasts. It is designed for use with the
RDA series of enclosures, in an AMX Lighting™ modular digital dimming
system. The module’s 120, 240, and 277 VAC ratings are CE, UL, and
C-UL approved.

RDM-HDC UL and C-UL Ratings

120 VAC, 50/60 Hz, 2400 W

240/277 VAC, 50/60 Hz, 2400 W

Control Out: 50 mA, 12 VDC

sourcing/sinking

Suggested Dimmed Loads

Four-wire dimmable ballasts

All low-voltage DC controlled ballasts

Specifications

Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 20 in-lbs. (2.3 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 1.3 lbs. (0.590 kg)

BTU/hr: 150

Control current: 150 mA @ 12 VDC

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Use low-voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

Test loads for shorts before connecting.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-HDC to the AMX Lighting Master

Lighting Application Drawings

Warning: Failure to ground the ballast may cause ballast
failure

FIG. 1 RDM-HDC

Low-voltage control
wiring: 4-pin

Relay

+ out (LV)

- out (LV)

Neutral

Line in

Load

High

Low-voltage

voltage

connector to AMX
Lighting master
controller

Mounting
points

FIG. 2 Connecting the RDM-HDC and AMX Lighting Master

FIG. 3 RDM-HDC application wiring

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

RDM-HDC 4-pin module connector

1 (+)

2 (DIM)

3 (-)

GND

4-pin plug from RDM series module

Note: The 4-pin plugs from the module connector to the 4-pin
connector on the master (black plug cover facing up).

RDM-HDC

LOAD LINE NEUT CON

Ballast

Florescent Ballast

Neutral
Line in (HOT)

Load

Neutral

+

-

Low-voltage wire rated
to 300 V

Circuit breaker
panel