4

ELECTRICAL CONNECTIONS

28

OPTISONIC 7300 / 8300

www.krohne.com

05/2012 - 7312262200 - AD EX OPTISONIC 7300/8300 R02

INFORMATION!
For converters with an

Ex e

terminal compartment, the compartment can be opened in an

energized state for short periods of time, to access the intrinsically safe terminals for possible
checks. However, the semi-circular insulation cover over the non-intrinsically safe mains supply
terminals L and N (or L+ and L-) MUST be kept closed.

Overview of possible "Ex ia" in-/outputs, defined by characters XYZ of the CG 36 numbers

Characters
XYZ

Name of I/O
circuits

Terminals
A, A-, A+

Terminals
B, B-

Terminals
C, C-

Terminals
D, D-

200

Exi-IO

n.c.

n.c.

CO(a)

PO/SO

300

n.c.

n.c.

CO

PO/SO

210

Exi-IO with Exi-

Option

CO(a)

PO/SO/CI

CO(a)

PO/SO

220

CO

PO/SO/CI

CO(a)

PO/SO

310

CO(a)

PO/SO/CI

CO

PO/SO

320

CO

PO/SO/CI

CO

PO/SO

230

Exi-IO with Exi-

Option 2

Iin

a

active

PO/SO/CI

CO(a)

PO/SO

330

Iin

a

active

PO/SO/CI

CO

PO/SO

240

Iin

p

passive

PO/SO/CI

CO(a)

PO/SO

340

Iin

p

passive

PO/SO/CI

CO

PO/SO

D00

Fieldbus I/O

Profibus PA

n.c.

n.c.

PA

PA

D10

Fieldbus I/O

Profibus PA

with Ex i Option

CO(a)

PO/SO/CI

PA

PA

D20

CO

PO/SO/CI

PA

PA

E00

Fieldbus I/O

Foundation

Fieldbus

n.c.

n.c.

FF

FF

E10

Fieldbus I/O

Foundation

Fieldbus with

Ex i Option

CO(a)

PO/SO/CI

FF

FF

E20

CO

PO/SO/CI

FF

FF

Used abbreviations for in-/output functions: CO = Current Output, PO = Pulse Output, SO = Status Output,

CI = Control Input, n.c. = not connected

All in-outputs are passive unless otherwise noted as active with extension (a).