Electrical connections, 4 shielding and grounding – KROHNE MFC 300 FOUNDATION FIELDBUS EN User Manual

Page 6

Advertising
background image

3

ELECTRICAL CONNECTIONS

6

MFC 300

www.krohne.com

02/2013 - 4001086702 - AD MFC 300 FF R02 en

All bus segments must be fitted with a terminator at both ends.

3.4 Shielding and grounding

• For optimum electromagnetic compatibility of systems it is extremely important that the

system components, and particularly the bus cables connecting the components, are
shielded and that such shields - if possible - form an unbroken cover.

• Hence, it follows that, for use in non-hazardous duty systems, the cable shield should be

grounded as often as possible.

• In Ex systems an adequate equipotential bonding in the hazardous and non-hazardous

location along the entire Fieldbus installation is strongly recommended. Multiple grounding
of the shield is of advantage.

• In explosion-proof systems the shielding must at least be connected at one end of the cable.
• NAMUR NE 21 compliance is given, provided the above recommended cable types are used.

Number of devices

Cable lengths for number of devices per branch line

1 device

2 devices

3 devices

4 devices

25...32

1 m / 3.3 ft

1 m / 3.3 ft

1 m / 3.3 ft

1 m / 3.3 ft

19...24

30 m / 100 ft

1 m / 3.3 ft

1 m / 3.3 ft

1 m / 3.3 ft

15...18

60 m / 200 ft

30 m / 100 ft

1 m / 3.3 ft

1 m / 3.3 ft

13...14

90 m / 300 ft

60 m / 200 ft

30 m / 100 ft

1 m / 3.3 ft

1..12

120 m / 400 ft

90 m / 300 ft

60 m / 200 ft

30 m / 100 ft

INFORMATION!
The use of twisted and shielded cables is strongly recommended, otherwise EMC protection of
the signal converter cannot be assured.