KROHNE OPTISWITCH 3100C 2wire EN User Manual

Page 22

Advertising
background image

Mode on the sensor

Level

Signal current - Sensor

Signal lamp - sensor

Fault signal

(min./max. mode)

any

<2.3 mA

flashes red

OPTISWITCH 3100 C level switch with signal conditioning

instrument

1)

The following chart provides an overview of the switching

conditions depending on the adjusted mode of the signal

conditioning instrument and the level.

Note:

Keep in mind that the mode switch of OPTISWITCH 3100 C

must be always set to "max.".

Mode on the signal

conditioning instru-

ment

Level

Signal current -

Sensor

Signal lamp - sensor Signal lamp - sig-

nal conditioning

instrument

Mode A

Overfill protection

approx. 8 mA

Green

Mode A

Overfill protection

approx. 16 mA

red

Mode B

Dry run protection

approx. 16 mA

red

Mode B

Dry run protection

approx. 8 mA

Green

1)

You will find suitable signal conditioning instruments under "Technical data"

22

OPTISWITCH 3100 C - with two-wire output

Set up

29955

-EN
-060830

Advertising