3 function chart – KROHNE OPTISWITCH 3200C 2wire EN User Manual

Page 22

Advertising
background image

min. - min.detection or dry run detection) on the signal

conditioning instrument.
When used on a control system, the following values apply:

l

Mode min.

- Vibrating element uncovered - 16 mA ±1 mA

-

Vibrating element covered - 8 mA ±1 mA

l

Mode max.

- Vibrating element uncovered - 8 mA ±1 mA

-

Vibrating element covered - 16 mA ±1 mA

Control lamp for indication of the switching condition.

l

green = 8 mA

l

red = 16 mA

l

red (flashing) = Failure (<2.3 mA)

6.3 Function chart

OPTISWITCH 3200 C level switch

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Mode on the sensor

Level

Signal current - Sensor

Signal lamp - sensor

max.

Overfill protection

8 mA

Green

max.

Overfill protection

approx. 16 mA

red

min.

Dry run protection

approx. 8 mA

Green

min.

Dry run protection

approx. 16 mA

red