Single channel architecture (1oo1d), The chronological sequence of pfd – KROHNE OPTISWITCH 5xx0C 2wire SIL EN User Manual
Page 9
Overflow protection
(max./A-operation)
Dry run protection
(min./B-operation)
λ
sd
35 FIT
141 FIT
λ
su
101 FIT
91 FIT
λ
dd
141 FIT
35 FIT
λ
du
25 FIT
35 FIT
MTBF = MTTF + MTTR
3.31 x 10
6
h
3.31 x 10
6
h
Fault reaction time
<
1.5 sec.
Single channel architecture (1oo1D)
SIL
SIL
2
HFT
0
Sensor type
Type A
Overflow protection
(max./A-operation)
Dry run protection
(min./B-operation)
SFF
91 %
88 %
PFD
avg
T
Proof
=
1 year
T
Proof
=
5 years
T
Proof
=
10 years
<
0.011 x 10
-2
<
0.055 x 10
-2
<
0.11 x 10
-2
<
0.016 x 10
-2
<
0.078 x 10
-2
<
0.155 x 10
-2
PFH
<
0.025 x 10
-6
/h
<
0.035 x 10
-6
/h
The chronological sequence of PFD
avg
is nearly linear to the operating
time over a period up to 10 years. The above values apply only to the
T
Proof
interval after which a recurring function test must be carried out.
Failure rates
Fault reaction time
Specific characteristics
Time-dependent proc-
ess of PFD
avg
OPTISWITCH series 5000 • - two-wire
9
1 Functional safety