Single channel architecture (1oo1d), The chronological sequence of pfd – KROHNE OPTISWITCH 5xx0C 2wire SIL EN User Manual

Page 9

Advertising
background image

Overflow protection

(max./A-operation)

Dry run protection

(min./B-operation)

λ

sd

35 FIT

141 FIT

λ

su

101 FIT

91 FIT

λ

dd

141 FIT

35 FIT

λ

du

25 FIT

35 FIT

MTBF = MTTF + MTTR

3.31 x 10

6

h

3.31 x 10

6

h

Fault reaction time

<

1.5 sec.

Single channel architecture (1oo1D)

SIL

SIL

2

HFT

0

Sensor type

Type A

Overflow protection

(max./A-operation)

Dry run protection

(min./B-operation)

SFF

91 %

88 %

PFD

avg

T

Proof

=

1 year

T

Proof

=

5 years

T

Proof

=

10 years

<

0.011 x 10

-2

<

0.055 x 10

-2

<

0.11 x 10

-2

<

0.016 x 10

-2

<

0.078 x 10

-2

<

0.155 x 10

-2

PFH

<

0.025 x 10

-6

/h

<

0.035 x 10

-6

/h

The chronological sequence of PFD

avg

is nearly linear to the operating

time over a period up to 10 years. The above values apply only to the
T

Proof

interval after which a recurring function test must be carried out.

Failure rates

Fault reaction time

Specific characteristics

Time-dependent proc-
ess of PFD

avg

OPTISWITCH series 5000 • - two-wire

9

1 Functional safety

32750

-

EN

-