KROHNE TIDALFLUX IFM 4110 PF EN User Manual

Page 14

Advertising
background image

7.30830.32.00

14

2.5.3.2 Pulse output A1 for electromechanical totalizers

PLEASE NOTE:
The output terminal A1 can be used as status output A1 or as a 2nd pulse output A1
for electromechanical totalizers.
Setting is as described in Fct. 3.07 HARDWARE.

Pulse output A1 is electrically connected to status output A2 (common centre grounding contact A

) but electrically

isolated from all other circuits.

All operating data and functions are adjustable, see Fct.1.07.

Active mode:

uses the internal power supply, terminals E+/E-

Passive mode:

requires external power supply, U

ext

32 V DC / 24 V AC, I

100 mA

(I

200 mA for polarized DC operation).

Max. adjustable frequency 50 kHz

Scaling

in pulses per unit of time (e.g. 10 pulses/s at Q

100%

flow) or

In pulses per unit of volume (e.g. 10 pulses/m

3

or US Gal).

Pulse width

symmetric, pulse duty factor 1:1, independent of output frequency,
automatic, with optimum pulse width,
pulse duty factor approx. 1:1 at Q

100%

, or

pulse width range from 0.01 to 1 s adjustable as required for corresponding lower output
frequency.

Forward/reverse flow measurement (F/R mode) is possible,

Connection diagrams see sect. 2.5.6

Schematic wiring diagram for pulse output A1 for electromechanical totalizers. This pulse output has a MOSFET switch
as output which switches direct and alternating voltages similar to a relay contact.

2.5.4

Status outputs A1 / A2 / D1 / D2

PLEASE NOTE:
The output terminal A1 can be used as status output A1 or as a 2nd pulse output A1 for electromechanical totalizers.
Setting is as described in Fct. 3.07 HARDWARE.

Status outputs A1/A2 and D1/D2 with the common centre grounding contacts A

and B

are electrically isolated from

each other and from all other circuits.

All operating data and functions are adjustable , see Fct. 1.07-1.10.

Active mode:

uses the internal power supply, terminals E+/E-

Passive mode:

requires external power supply, U

ext

32 V DC / 24 V AC, I

100 mA

(I

200 mA for A1 in case of polarized DC operation).

The following operating conditions can be signaled using the status outputs:
-

flow direction (F/R mode)

-

limits

-

error messages

-

active range in case of range change-over

-

inverse operation of A1 and A2 or D1 and D2,

i.e. used as change-over switch with common centre grounding contact A

or D

.

A1

A

Advertising