Section 1 – Main safety-relevant characteristics

10/2001

BM 100 A ATEX

5



0DLQVDIHW\UHOHYDQWFKDUDFWHULVWLFV

1.1 Approved

categories

1.1.1

1/2 G and 1/2 D

The signal converter is installed in hazardous locations requiring Category 2 G or 2 D equipment.
The probe is installed in hazardous locations requiring Category 1 G or 1 D equipment. The
devices are suitable for use in explosive atmospheres of all flammable substances of Gas Group
IIA, IIB and IIC.

Please take note of the following exceptions:

Plastic-coated probes may not be used in connection with Gas Group IIC substances.

Devices with plastic-coated probes may not be used for applications requiring Category 1/2 D
equipment, unless effective measures have been taken to avoid electrostatic discharge.

1.1.2

2 G and 2 D

BM 100 A level gauges are installed in areas requiring Category 2 G or 2 D equipment. The
devices are suitable for use in explosive atmospheres of all combustible substances of Gas Group
IIA, IIB and IIC.

Please take note of the following exceptions:

Plastic-coated probes may not be used in connection with substances of Gas Group IIC.

Devices with plastic-coated probes may not be used for applications requiring Category 2 D
equipment, unless effective measures have been taken to avoid electrostatic discharge.

1.2

Electrical limits

1.2.1

Intrinsically safe I/O functions

Intrinsically safe circuits for I/O functions of the BM 100 A are safety-separated from ground and
also from each other (test voltage > 500 V AC). In addition, all intrinsically safe circuits are safety-
separated from the non-intrinsically safe power circuits up to a peak voltage of 375 V.

Only certified intrinsically safe equipment with EEx ia IIC type of protection may be connected to
the I/O output circuits. This requirement applies independent of the required category and also in
cases where the device is not operated in the hazardous location.