Electrical connections, 4 grounding the measuring device, 5 description of the current output – KROHNE OPTIBAR P 3050 C EN User Manual

Page 22

Advertising
background image

4

ELECTRICAL CONNECTIONS

22

OPTIBAR P 3050 C

www.krohne.com

03/2012 - 4001953401 - MA OPTIBAR P3050C R02 en

4.4 Grounding the measuring device

• The pressure sensor must be properly grounded.
• When using an intrinsically safe or grounded feed unit, do not connect PE!
• Do not use the grounding cable to connect any other electrical devices to ground at the same

time.

• The pressure transmitter is connected to ground by means of a functional grounding

conductor.

• In hazardous areas, grounding is used at the same time for equipotential bonding.

A ground terminal is provided on the outside of the housing to accommodate wire widths of up to
1.5 mm

2

.

4.5 Description of the current output

The current output is a 2-wire 4...20 mA output.

Overload condition:

• Lower limit: 3.8 mA
• Upper limit: 20.5 mA

Alarm current:

• Low alarm current: 3.6 mA
• High alarm current: 21 mA

Standard setting: High alarm current
The transmitter works with voltages of 12...45 VDC, no load.

R

Load

[KΩ] = (U

B

[V] - 12 V) / alarm current max. [mA]

where U

B

= supply voltage and R

Load

= max. load resistance (load)

DANGER!
There should be no difference in potential between the pressure sensor and the housing or
protective earth of the transmitter!

Figure 4-5: Position of the ground terminal on the housing

1 Ground terminal

.book Page 22 Thursday, March 8, 2012 9:29 AM

Advertising