Supplementary Installation and Operating Instructions UFC 030 HART

HC275, FC375, AMS, PDM

1 General

Information

The UFC 030 is a “four-wire” transmitter with 4...20mA current output and HART

 capability. Dependent on device

implementation it is available with active/passive current output (standard) or passive current output (MODIS).

General Characteristics of the UFC 030 HART

 interface:

• Multidrop Mode is supported

• Burst Mode is not supported

Electrical connection: Refer to section “Electrical connection of the signal inputs and outputs” of the following manual:

• “Installation and Operating Instructions Universal 3-Beam ultrasonic flowmeter UFM 3030 Compact

ultrasonic flowmeter UFC 030 Ultrasonic flow converter UFS 3000 Ultrasonic flow sensor” (KROHNE)


There are two ways of using the HART

 communication:


a) As a point-to-point connection between the UFC 030 and the HART

 master equipment. The instrument's current

output may be active or passive.

Point-to-Point Analog/Digital Mode

4

20

mA

4...20 mA

Power
Supply

250 Ω

HART

Modem

HART

Analog

Primary Master

Secondary Master

UFC 030

Addr. 0

For slaves with
passive current
output (2 wire)

Terminal I/C

Terminal