5 configuration examples – KROHNE BM 70 M User Manual

Page 39

Advertising
background image

BM 70 M

39

Function (Fct.)

Enter range

Default value

Description

3.6.3

THRESHOLD

Value
-200.00 ... +200.00 [m]
0.00 ... 99999.99 [m3]

0 ... 100 [Refl.]

5.00 m
5.00 m3
50

Input of the threshold
value for the
switching output.
(Input is dependent
on the function of the
switching output. The
values for level and
distance include the
tank bottom and
reference offset,
resp.)

3.6.4

HYSTERESIS Value

0.00 [m] ... Tank height
0.00 ... 99999.99 [m3]

0 ... 100 [Refl.]

0.10 m
0.10 m3
10

Input of the
hysteresis for the
switching output.
(Input is dependent
on the function of the
switching output.)

*:Default values following a parameter reset (use of a new EEPROM not yet described).
The factory setting for the parameters marked with * is dependent upon the device version and
customer specifications (if the tank height is known at the time the order is placed).

8.5 Configuration

examples

Sump

non-
measurable
zone

tank height

(Fct. 3.1.1)

Fct. 3.1.4

upper reference point

(top edge of tank connecting flange)

block distance (Fct. 3.1.2)

response

current output

20
mA

Imax
(Fct. 3.3.4)

4

Imin
(Fct. 3.3.3)

lower reference point
(tank bottom / datum point)

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

Fct. 3.1.5

threshold

measuring

mA

range