KYORITSU 3131A User Manual

Page 7

Advertising
background image

― 5 ―

Typical Number of Measurements

(central tendency for supply voltage up to

6.5V)

Insulation Resistance Ranges:

1000V/400MΩ Range

Approx. 500 times min.

500V/200MΩRange

Approx. 1300 times min.

250V/100MΩ Range

Approx. 1800 times min.

Continuity Test (Resistance Test) Ranges:

xΩ Range/ x 10Ω Range

Approx. 1000 times min.

Applicable Standards

IEC 61010-1

Overvoltage CAT.300V Pollution Degree 2

IEC 61010-2-31

Safety requirements for hand-held probe assemblies

IEC 61557-1/2/4

Measuring equipment for low voltage distribution systems

IEC 61326

EMC

IEC 60529 (IP54) Dust & drip proof

Operating Temperature & Humidity:

0-40°

C, relative humidity up to 85%

Storage Temperature & Humidity:

-20-60°

C, relative humidity up to 85%

Insulation Resistance

More than 50MΩat 1000V DC between
electrical circuit and housing case

Withstand Voltage

3700V AC for one minute between electrical
circuit and housing case

Overload Protection

Insulation resistance ranges:

1000V Range 1200V (DC+AC p-p) for 10 seconds
500V Range

600V (DC+AC p-p) for 10 seconds

250V Range

300V (DC+AC p-p) for 10 seconds

Continuity ranges:

xΩ/ x 10ΩRange 280V (DC+AC p-p) for 10 seconds

Dimensions:

185(L) x 167(W) x 89(D) mm approx.

Weight:

860g approx. (including batteries)

Power Source:

6 x 1.5V battery type SUM-3, R-6 , AA or equivalent

Accessories

Test Probe MODEL7122

x 1 set

Strap belt

x 1

Test probe pouch

x 1

R6P AA batteries

x 6

Spare fuse F 500mA/600V

x 1

Instruction manual

x 1

Advertising