KYORITSU 8035 User Manual

Non-contact safety phase indicator

Advertising
background image

2. Features

● This is a Phase indicator and can indicate a presence of live

line and phase sequence with the equipped LED and Buzzer

while clipping the 3-phase line over the jacket of a conductor.

● Brightness switch is equipped to make the indication visible

in dimly lit areas.

● A magnet on the backside of the instrument can fix the

instrument onto the distribution board and enables safety and

easy measurements.

● Designed to International safety standard IEC 61010-1 (CAT.

III 1000V/ CAT.IV, 600V, Pollution degree 2)

3. Instrument layout

● Put insulated protective gears when there is a danger of

electrical shock hazard.

● The tip of clip is made of metal and it is not completely

insulated. Be especially careful about the possible shorting

where the measured object has exposed metal parts.

● Never attempt to use the instrument if it's surface or your

hand is wet.

Otherwise, electrical shock accident may occur.

● Never open the Battery compartment cover and the

instrument case when making a measurement.

● The instrument is to be used only in its intended applications

or conditions. Otherwise, safety functions equipped with the

instrument doesn’t work, and instrument damage or serious

personal injury may be caused.

● Only the qualified person can use the instrument at the

secondary side of high voltage power receiving equipments.

#

WARNING

● Never attempt to make any measurement, if any abnormal

conditions are noted, such as broken case, and exposed

metal parts.

● Do not install substitute parts or make any modification to the

instrument. Return the instrument to your local Kyoritsu distributor

for repair or re-calibration in case of suspected faulty operation.

● Always keep your fingers and hands behind the barrier on

the instrument to avoid the possible shock hazard.

● Do not tr y to replace batteries if the sur face of the

instrument is wet.

Disconnect the clips from the measured conductors first

and power off the instrument before opening the Battery

compartment cover for a battery replacement.

#

CAUTION

● Do not apply shocks, vibrations or excessive forces onto the

Measurement clips.

● Never force to open the Measurement clips when they are

frozen.

● This instrument can be operated with safe at temperatures

between -10ºC and 50ºC and altitude up to 2000m.

● Keep away from dust and water.

● Precise measurement cannot be made near a charged body

or equipment generating electromagnetic waves.

● Measurable conductor size is between dia. 2.4mm and

30mm. Accurate measurements for conductors out of this

range cannot be made.

● Measured results are influenced by voltage wires on which

twice or more of the measured voltages exist near the point

to be clipped.

The clip point should be far from such voltage wires.

● This instrument cannot identify wiring status correctly when an

earth line is connected between phases via delta connection.

Check the connection specification of the measured object.

● Incapable of measuring bus bars or shielded wires. Clip onto

a covered conductor and make a measurement.

● All the clips should be clipped onto the covered wires and

make measurements. Otherwise, it may cause a malfunction.

1. Safety Warnings

This instrument has been designed, manufactured and tested

according to following standards and delivered in the best

condition after passing quality control tests.

● IEC61010-1 Measurement CAT.III 1000V/CAT.IV 600V

Pollution degree 2

● IEC61010-031

This instruction manual contains warnings and safety rules which

have to be observed by the user to ensure safe operation of the

instrument and to maintain it in safe condition. Therefore, read

through these operating instructions before using the instrument.

#

WARNING

● Read through and understand instructions contained in this

manual before using the instrument.

● Keep the manual at hand to enable quick reference whenever

necessary.

● The instrument is to be used only in its intended applications.

● Understand and follow all the safety instructions contained

in the manual.

It is essential that the above instructions are adhered to.

Failure to follow the above instructions may cause injury and

or instrument damage.
The symbol # indicated on the instrument, means that the

user must refer to the related parts in the manual for safe

operation of the instrument.

It is essential to read the instructions wherever the symbol

appears in the manual.
#

DANGER is reserved for conditions and actions that are

likely to cause serious or fatal injury.

#

WARNING is reserved for conditions and actions that can

cause serious or fatal Injury.

#

CAUTION is reserved for conditions and actions that can

cause minor injury or instrument damage.

#

DANGER

● Confirm a proper operation of the instrument with a well-

known power supply.

● Warning LED might not light up at live status. (earth potential

70V or less). Never touch the wire.

● Voltages may exist when the Live LED is flashing (indicating

Earth phase). Never touch with the wires.

● Never make measurement on a circuit in which the earth

potential exceeds 1000V to avoid electrical shocks.

● Do not make measurement when thunder is rumbling. If the

instrument is in use, stop the measurement immediately and

remove the instrument from the measured object.

● Do not attempt to make measurement in the presence of

flammable gasses. Otherwise, the use of the instrument

may cause sparking, which can lead to an explosion.

● Keep your fingers and hands behind the barrier on the

instrument to avoid the possible shock hazard.

● Do not touch the Clips during measurements to get accurate

results.

● This instrument cannot find the missing line of the earth line.

● Do not pull the cable when removing the Measurement clips

from the measured conductors. It may cause a break in cable.

● Power off the instrument after use. Remove the batteries

if the instrument is to be stored and will not be in use for a

long period.

● Do not expose the instrument to direct sunlight, high-

temperature and humidity or dew.

● Dry and store the instrument if it is wet.

● Do not step on or pinch the cord to prevent the jacket of

cable from being damaged.

● Bending or pulling the cord may cause a break in a cord.

● Never give shocks, such as vibration or drop, which may

damage the instrument.

● Use a damp cloth and detergent for cleaning the instrument.

Do not use abrasives or solvents.

Safety Symbols

#

Refer to the instructions in the manual to protect the

user and instrument.

Indicates instrument with double or reinforced insulation

AC
This instrument satisfies the marking requirement defined

in the WEEE Directive. This symbol indicates separate

collection for electrical and electronic equipment.

○ Measurement categories(Over-voltage categories)

To ensure safe operation of measuring instruments, IEC 61010

establishes safety standards for various electrical environments,

categorized as CAT I to CAT IV, and called measurement categories.

Higher-numbered categories correspond to electrical

environments with greater momentary energy, so a measuring

instrument designed for CAT III environments can endure

greater momentary energy than one designed for CATII.
CAT I : Secondary electrical circuits connected to an AC

electrical outlet through a transformer or similar device.

CAT II : Primary electrical circuits of equipment connected to

an AC electrical outlet by a power cord.

CAT III : Pr imar y electr ic al circuits of the equipment

connected directly to the distribution panel, and

feeders from the distribution panel to outlets.

CAT IV : The circuit from the service drop to the service

entrance, and to the power meter and primary

overcurrent protection device (distribution panel).

4. Specification

Model

KEW8035

Measurement

principle

Static induction

Voltage range

3-phase AC70 to 1000V

(voltage to earth, continuous sine wave)

Frequency range

45 to 66Hz

Operating

temperature &

humidity range

-10 to 50ºC, relative humidity 80% or less

(no condensation)

Storage

temperature &

humidity range

-20 to 60ºC, relative humidity 80% or less

(no condensation) (*1)

Location for use

Altitude 2000m or less, Indoor use

Applicable

standards

IEC 61010-1

Measurement CAT.III 1000V/CAT.IV 600V

Pollution degree 2

IEC61010-031

IEC 61326-1,2-2 (EMC standard)

IEC 61557-1,7

Dust-proof

IP40 (IEC60529)

Withstand

voltage

AC6880V (rms 50/60Hz) for 5 sec

between the tip of Measurement clip and enclosure

Insulation

resistance

10MΩ or more/ 1000V

between the tip of Measurement clip and enclosure

Power source

DC6V

(size AA alkaline battery LR6 or equivalent

1.5V AA × 4pcs)

Auto-power-off

10 min after powering on the instrument

Low battery

warning

Power LED flashes at 4.0±0.2V or less (*2)

Current

consumption

15mA (*3)

Continuous use

approx 200 hours (*4)

Conductor size External diameter of the covered conductor

Dia.2.4 to 30mm

Cable length

approx 70cm

Dimension

112(L) × 61(W) × 36(D)mm

Weight

approx 380g (batteries included)

Accessories

Instruction manual, battery, Soft case, Label for Clip

(*1) without batteries

(*2) powers off automatically at 3±0.2V or less

(*3) stand-by state (will be doubled (max) at measurement)

(*4) stand-by state (will be 0.5 times at measurement)

5. Checks and Indications

5.1. Preliminary checks

5.1.1. Press the Power switch and power on the instrument.

Then all the LEDs flash in order for about 1 sec. Confirm

all the LEDs light up and flash. Only the Power LED

keeps lighted up in about 1 sec later.

5.1.2. Apex of “▼” mark on the Measurement clip shall

indicate the center of the measured conductor. Connect

each Measurement clip to 3-phase line as follows:

Red to L1, Phase-U, White to L2, Phase-V, Blue to L3,

Phase-W.

5.1.3. Measure a covered conductor AC70V or more first

to confirm each live LED lights up. Do not use the

instrument when any of the LED doesn’t light up.

5.1.4. Presence of live wires and phase sequence are

informed by LED indication and Buzzer sound as soon

as connecting the clips.

5.2. Live wire check

#

DANGER

● LEDs don’t light up when voltage to earth is 70V or less.

● Voltages may exist at Earth phase.

#

CAUTION

● It is impossible to detect the missing phase of the earth line.

Earth line and phase sequence are indicated if the earth line

has a missing phase.

State

Indication

Live

Phase with flashing LED is

live state.

Missing line

or

Earth line

LED doesn’t light up for

missing line or earth line.

Earth line

(Delta

connection)

Phase with flashing LED is

an earth phase.

Positive

phase

When the green Rotation

LED flashes in the order of

the direction indicated by

the arrow mark (clockwise),

the circuit under test has a

positive phase.

The buzzer sounds

intermittently. (pi-pi-pi)

Reversed

phase

When the red Rotation

LED flashes in the order

of the direction indicated

by the arrow mark

(counterclockwise), the

circuit under test has a

reversed phase. The buzzer

sounds continuously. (pi---)

5.3. Use the Brightness switch to make the LED indication

brighter.

Brightness of all the LEDs (except for the Power LED) is

increased while pressing down the switch.

6. Battery Replacement

#

CAUTION

● Power off the instrument and remove the Measurement clips

from the measured object when replacing batteries to avoid

electrical shocks.

● Do not mix old and new batteries.

● Install batteries in correct polarity as indicated inside the

case.

● Use the same model of batteries from the same manufacturer.

When the Power LED on the front side of the instrument is

flashing, battery voltage is low. Replace batteries with new

ones to continue further measurements.

Low battery voltage may not affect measurement accuracies.

The instrument is powered off automatically when batteries are

exhausted.

1) Loosen the screw fixing the Battery compartment cover.

2) Slide the Battery compartment cover downwards to remove

it.

3) Replace the batteries with new ones. Four size AA LR6

alkaline or equivalent 1.5V AA type batteries should be

used.

4) Install the Battery compartment cover and tighten the screw.

Instruction Manual

Non-Contact Safety Phase Indicator

KEW

8035

09-01

92-2009

Barrie

Measurement clip

Test leads

Live LED (L1, Phase-U)
Live LED (L2, Phase-V)
Live LED (L3, Phase-W)

Phase sequence LED (positive)
Phase sequence LED (reversed)
Rotation LED (positive)
Rotation LED (reversed)

Power switch

Power LED

Brightness switch



Put the Label for clip,

if necessary.

Lines connecting the apexes

of “▼” marks should pass

through the center of the

conductor.

Screw

Battery compartment

cover

DISTRIBUTOR

Kyoritsu reserves the rights to change specifications or designs
described in this manual without notice and without obligations.

Advertising