INSTRUCTION MANUAL

KEW 8121/8122/8123

CLAMP SENSOR

Series

CLAMP SENSOR

KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD.,

TOKYO, JAPAN

KEW8121

KEW8122

KEW8123

1. Safety warnings

This instrument has been designed, manufactured and
tested according to IEC 61010: Safety requirements for
Electronic Measuring apparatus, and delivered in the
best condition after passing quality control tests. This
instruction manual contains warnings and safety rules
which have to be observed by the user to ensure safe
operation of the instrument and to maintain it in safe
condition. Therefore, read through these operating
instructions before using the instrument.

WARNING

● Read through and understand instructions contained

in this manual before using the instrument.

● Keep the manual at hand to enable quick reference

whenever necessary.

● The instrument is to be used only in its intended

applications.
The operating instructions described in the manual
must be observed.

● Understand and follow all the safety instructions

contained in the manual.
It is essential that the above instructions are adhered
to. Failure to follow the above instructions may cause
injury and or instrument damage.

The symbol indicated on the instrument, means that
the user must refer to the related parts in the manual
for safe operation of the instrument. It is essential to
read the instructions wherever the symbol appears
in the manual.

DANGER is reserved for conditions and actions that
are likely to cause serious or fatal injury.
WARNING is reserved for conditions and actions
that can cause serious or fatal Injury.
CAUTION is reserved for conditions and actions that
can cause minor injury or instrument damage.

DANGER

● Never make measurement on a circuit in which the

electrical potential exceeds AC300V using KEW8121
and AC600V using KEW8122 and 8123.

● Do not make measurement when thunder rumbling. If the

instrument is in use, stop the measurement immediately
and remove the instrument from the measured object.

● Do not attempt to make measurement in the presence of

flammable gasses. Otherwise, the use of the instrument
may cause sparking, which can lead to an explosion.

● The transformer jaws are made of metal and their tips

are not completely insulated. Be especially careful
about the possible shorting where the measured
object has exposed metal parts.

● Never attempt to use the instrument if it's surface or

your hand are wet.

● Do not exceed the maximum allowable input of any

measuring range.

WARNING

● Never attempt to make any measurement, if any

abnormal conditions are noted, such as broken case,
and exposed metal parts.

● Do not install substitute parts or make any

modification to the instrument.
Return the instrument to the distributor from who you
purchased this instrument for repair or re-calibration in
case of suspected faulty operation.

● Always keep your fingers and hands behind the barrier

on the instrument to avoid the possible shock hazard.

CAUTION

● Do not step on or pinch the cord to prevent the jacket

of cord from being damaged.

● The output connector shall be removed or connected

without clamping a conductor. Otherwise, it may cause
a failure.

● Do not expose the instrument to direct sunlight, high

temperatures, humidity or dew.

● Never give shocks, such as vibration or drop, which

may damage the instrument.

● Use a damp cloth and detergent for cleaning the

instrument. Do not use abrasives or solvents.

Safety symbols

F

Refer to the instructions in the manual.

Indicates a Instrument with double or reinforced insulation

Indicates that this instrument can clamp on live bare

conductors when the voltage to be tested is below

Circuit - Ground-to-Earth voltage against the indicated

Measurement Category.

Indicates AC

Transformer

Interior wiring

Incoming wire

CAT.Ⅳ

CAT.Ⅰ

CAT.Ⅱ

CAT.Ⅲ

Socket

○Measurement categories(Over-voltage categories) To

ensure safe operation of measuring instruments, IEC
61010 establishes safety standards for various electrical
environments, categorized as CATto CAT, and called
measurement categories.

Higher-numbered categories correspond to electrical
environments with greater momentary energy, so a
measuring instrument designed for CATenvironments
can endure greater momentary 0energy than one
designed for CAT.

CAT: Secondary electrical circuits connected to an AC

electrical outlet through a transformer or similar
device.

CAT: Primary electrical circuits of equipment connected

to an AC electrical outlet by a power cord.

CAT: Primary electrical circuits of the equipment

connected directly to the distribution panel, and
feeders from the distribution panel to outlets.

CAT: The circuit from the service drop to the service

entrance, and to the power meter and primary
overcurrent protection device (distribution panel).

2. Features

● Clamp sensor for AC current measurement.
● Designed to international safety standard IEC61010-2-032

CAT.Pollution Degree 2

KEW8121 CAT.300V
KEW8122 /8123 CAT.600V

3. Instrument layout

4. DIN Plug pin assignment

3: GND pin
5: Output signal pin
6: Sensor Signal pin

(Resistance between 3Pin and 6Pin:

8121:62kΩ 8122:11kΩ 8123:24kΩ)

1, 2 and 4: No use

*Lower figure shows the pin assignment seeing the Clamp

sensor from output connector part. The figure of the pin
assignment of connection terminal is symmetrical to lower
figure.

5

3

1

2

4

6

Transform Jaws

Trigger

Cable

Output connector

Barrier

92―1734

05-02

DISTRIBUTOR

KYORITSU ELECTRICAL

INSTRUMENTS

WORKS, LTD.

No.5-20, Nakane 2― chome, Meguro-ku,
Tokyo, 152-0031 Japan
Phone:81-3-3723-0131 Fax:81-3-3723-0152
URL:http://www.kew-ltd.co.jp
E-mail:[email protected]
Factories:Uwajima&Ehime

5. Operating instructions

DANGER

● Never make measurement on a circuit in which the

electrical potential exceeds AC300V using KEW8121
and AC600V using KEW8122 and 8123 in order to
avoid possible shock hazard.

● The transformer jaws are made of metal and their tips

are not completely insulated. Be especially careful
about the possible shorting where the measured
object has exposed metal parts.

CAUTION

● Take sufficient care to avoid shock, vibration or

excessive force when handling the instrument.
Otherwise, precisely adjusted transformer jaws will be
damaged.

● When transformer jaws do not fully close, never try to

close them by force, but make them free to move and
try again. If a foreign substance is stuck in the jaw
tips, remove it.

● When making current measurements, keep the

transformer jaws fully closed.

Otherwise, accurate measurements cannot be taken.
Maximum conductor size is as follows.

KEW8121 : 24mm in diameter
KEW8122 : 40mm in diameter
KEW8123 : 55mm in diameter

● Hold the inserting part (except for the cable) and

disconnect the Output connector from the measuring
instrument so as not to cause a break in the cord.

Measurement procedures
(1) Connect the Output connector to the Input terminal of

the measuring instrument.

(2) Press the Trigger to open the transformer jaws and

clamp onto one conductor.

In this case, the measured conductor shall be at the
center of the jaws.

(3) Ensure that the tips of transformer jaws are firmly closed.

Conductor

MINI DIN 6PIN

50MΩ or greater at 1000V
between Jaw and enclosure
between enclosure and output terminal
between Jaw and output terminal

Model

Rated voltage

Output voltage

Measuring range

Accuracy

(Input: sine wave)

Temperature & humidity range

(Guaranteed accuracy)

Operating temperature range

Storage temperature range

Maximum permissible input

Output

impedance

Location for use

Applicable

standards

Withstand

voltage

Insulation

resistance

Conductor Size

Dimension

Cable length

Output terminal

Weight

Accessories

Option

6.Specifications

23±5℃, relative humidity: 85% or less (no condensation)

0∼40℃, relative humidity: 85% or less (no condensation)

-20∼60℃, relative humidity: 85% or less (no condensation)

Altitude up to 2000m, Indoors

IEC 61010-1, IEC 61010-2-032
Measurement CAT. (300Vrms)
Pollution degree 2
IEC 61326I

IEC 61010-1, IEC 61010-2-032
Measurement CAT. (600Vrms)
Pollution degree 2
IEC 61326

Approx. 2m

Instruction manual
Cable marker

Approx. 360g

Approx. 260g

Approx. 150g

170(L)×105(W)×48(D)mm

128(L)×81(W)×36(D)mm

97(L)×59(W)×26(D)mm

Approx.55mm in diameter (max.)

Approx.40mm in diameter (max.)

Approx.24mm in diameter (max.)

AC3540Vrms (50/60Hz)for 5 sec.
between Jaw and enclosure
between enclosure and output terminal
between Jaw and output terminal

AC5350Vrms (50/60Hz)for 5 sec.
between Jaw and enclosure
between enclosure and output terminal
between Jaw and output terminal

Approx. 1.5Ω

Approx. 1.9Ω

Approx. 9.5Ω

AC1000Arms continuous (50/60Hz)

AC500Arms continuous (50/60Hz)

AC100Arms continuous(50/60Hz)

±2.0%rdg±0.3mV

(50/60Hz)

±3.0%rdg±0.5mV

(40∼1kHz)

±2.0%rdg±0.3mV

(50/60Hz)

±3.0%rdg±0.5mV

(40∼1kHz)

±2.0%rdg±0.3mV

(50/60Hz)

±3.0%rdg±0.5mV

(40∼1kHz)

AC0∼1000A

AC0∼500A

AC0∼100A

AC0∼500mV
(AC500mV/AC1000A):0.5mV/A

AC0∼500mV
(AC500mV/AC500A):1mV/A

AC0∼500mV
(AC500mV/AC100A):5mV/A

AC1000Arms(1414Apeak)

AC500Arms(707Apeak)

AC100Arms(141Apeak)

KEW 8123

KEW 8122

KEW 8121

MODEL 7146(Banana φ4 adjuster plug)
MODEL 7147(Extension cable)