Lake Monitors FlowStat ES Sensor (Plastic) User Manual

Page 3

Advertising
background image

Mechanical Specifications

FLOW SENSOR WITH STAINLESS STEEL BODY

Maximum pressure:

200 PSI clear cover, 500 PSI SS cover

Maximum temperature: 225ºF

Measuring range*
1/2" NPT Ported:

0.5 - 15 GPM

3/4" & 1" NPT Ported:

1.5 - 50 GPM

Wetted materials:

316SS, acetal copolymer, Buna, PEEK
and polycarbonate

Non-wetted materials:

Epoxy, Lexan

®

and PVC

FLOW SENSOR WITH POLYPROPYLENE BODY

Maximum pressure:

150 PSI

Maximum temperature: 150ºF

Measuring range*
1/2" NPT Ported::

0.5 - 15 GPM

Wetted materials:

316SS, acetal copolymer, Buna, PEEK,
polycarbonate and polypropylene

Non-wetted materials:

Epoxy, Lexan

®

and PVC

*Important: Chose a maximum flow rate. For 1/2": 5 - 15 maximum GPM.

For 3/4" and 1": 15 - 50 maximum GPM. Minimum flow rate will
be 10% of maximum flow rate. Example: If your maximum flow
rate is 8 GPM, the minimum flow rate would be .8 (8 x .1 = .8).
Thus, the correct flow range would be .8 - 8.0 GPM.

Electronic Specifications

ALL VERSIONS WITH 4-20 MA CIRCUIT

Power requirements:

12-35V

DC

, 20mA

Load driving capacity:

Max. Load (

) = 50(Power Supply Voltage - 12)

Trans. Distance:

limited only by wire resistance & supply voltage

LED:

provides power indication

Flow rate accuracy:

±2% of full scale

Repeatability:

±0.5% of scale

Resolution:

infinite

Response time:

2 seconds to 90%

Over-current protection: self limiting at 30mA

Fail safe indication:

4 mA

(10)

Installation - Mechanical

1. The FlowStat has NPT (National Pipe Thread) plumbing con-

nections. Lake Monitors recommends that a paste type pipe
sealant be used on these threads. [Thread sealant can
be used as long as it is applied in such a way that it will not enter
the flow stream. Pieces of thread seal tape can wrap around the
turbine and impede its rotation.]

2. The recommended mounting orientation would be any plane that

will place the axis of the turbine horizontal with respect to the
ground. See Illustration 1. The unit will operate satisfactorily with
its axis at angles other than horizontal, but side loading of the
bearing surfaces will lead to premature wear of the rotating parts.

3. For the best flow measurement results, place the inlet (See Note 1)

of the flow sensor at least 10 straight pipe diameters down-
stream from any fitting, valve, elbow, reducer, etc. that causes
non-stable flow conditions. Ideally, 5 straight pipe diameters should
be placed at the outlet of the sensor. If the sensor must be placed
closer to a source of non-stable flow than these recommended dis-
tances, some instability of the output signal may result. The aver-
age signal will be accurate.

(3)

Illustration 1:

Mounting Instructions