NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual

Page 24

Advertising
background image

24

1

For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.

2

An attempt to exceed a limit will set the register to its high or low limit value.

Calculation Display Rounding Factor

Calculation Filter Band

A=Input A, B=Input B, C=Calculation Constant

0=1 Rdg/sec, 1=2 Rdgs/sec, 2=5 Rdgs/sec,
3=10 Rdgs/sec, 4=20 Rdgs/sec

1=1 Display Unit

1=1 Display Unit

0=Auto, 1=Latch1, 2=Latch2

0=Auto, 1=Latch1, 2=Latch2

Read/Write

Read/Write

Read/Write

Read/Write

2

2

0

0

65000

65000

2

2

1

1

0

0

0=Max Update Rate, 1=0.1 sec

0=Max Update Rate, 1=0.1 sec

SEE MODULE 6 FOR DESCRIPTION OF PARAMETERS
(APPLIES ONLY IF SP OPTION CARD, IS INSTALLED)

Hysteresis

Hysteresis

Reset

Reset

40363

40373

40367

40377

1=0.1 Second

1=0.1 Second

0=No, 1 = Yes

0=No, 1 = Yes

0=Second, 1=Minute, 2=Hour, 3=Day

Read/Write

0=Off, 1=On

0=0, 1=0.0, 2=0.00, 3=0.000, 4=0.0000

1=0.1 Second

0=1, 1=2, 2=5, 3=10, 4=20, 5=50, 6=100

1=1 display unit

0=A-Rel, 1=A-Abs, 2=b-Rel, 3=bAbs, 4=Calc

0=A-Rel, 1=A-Abs, 2=b-Rel, 3=bAbs, 4=Calc

Read/Write

Read/Write

Read/Write

Read/Write

0

0

0

0

32750

32750

1

1

0

0

0

0

On Delay

On Delay

Standby

Standby

40364

40374

40368

40378

1=0.1 Second

1=0.1 Second

0=Off, 1=Normal, 2=Reverse, 3=Flash

0=Off, 1=Normal, 2=Reverse, 3=Flash

Read/Write

Read/Write

Read/Write

Read/Write

0

0

1

1

32750

32750

3

3

0

0

1

0

Off Delay

Off Delay

Lit - Annunciator

Lit - Annunciator

40365

40375

40369

40379

Read/Write

Read/Write

10

10

32750

32750

0

0

Max (Hi) Capture Delay Time

Min (Lo) Capture Delay Time

40332

40334

SETPOINT 1 OUTPUT PARAMETERS

Note: SP Values are located at Registers 40013-40021

SETPOINT 2 OUTPUT PARAMETERS

Read/Write

Read/Write

0

0

6

6

0

0

Assignment

Assignment

40361

40371

0=No, 1=Ab-HI, 2=Ab-Lo, 3=AU-HI, 4=AU-LO,
9=totLo, 10=totHI; Do not use 5-8.

0=No, 1=Ab-HI, 2=Ab-Lo, 3=AU-HI, 4=AU-LO, 5=dE-HI,
6=dE-LO, 7=bANd, 8=bNdIn, 9=totLo, 10=totHI

0=Normal, 1=Reverse

0=Normal, 1=Reverse

Read/Write

Read/Write

Read/Write

Read/Write

0

0

0

0

10

10

1

1

0

0

0

0

Action

Action

Output Logic

Output Logic

40362

40372

40366

40376

1

3

0

Total Timebase

40353

1=0.001

Read/Write

1000

65000

0

Total Scale Factor

40354

Read/Write

-19999

99999

-19999

Total Low Cut Value (Hi word)

40355

0 = No, 1 = Yes

Read/Write

Read/Write

-19999

0

99999

1

-19999

0

Total Low Cut Value (Lo word)

Total Reset at Power Up

40356

40357

TOTALIZER PARAMETERS

0=A-Rel, 1= b-Rel, 2= Calc

Read/Write

0

2

0

Total Assignment

40351

0=0, 1= 0.0, 2=0.00, 3=0.000, 4=0.0000

Read/Write

2

4

0

Total Decimal Point

40352

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

0

3

10

1000

0

10

1

4

250

99999

6

250

0

0

0

-19999

0

0

Units Annunciator Backlight

Calculation Display Decimal Point

Calculation Constant Value Low

Calculation Display Filter Value

Calculation Constant Value High

40336

40338

40340

40342

40339

40341

40343

Read/Write

Read/Write

0

0

4

5

0

0

Display Update Time

Calculation Function

40335

40337

Read/Write

Read/Write

0

0

4

4

0

0

Max (Hi) Value Assignment

Min (Lo) Value Assignment

40331

40333

SECONDARY PARAMETERS (Continued)

SEE MODULE 4 FOR DESCRIPTIONS OF PARAMETERS

COMMENTS

ACCESS

FACTORY

SETTING

HIGH LIMIT

2

LOW LIMIT

2

REGISTER NAME

REGISTER

ADDRESS

1

0 = C+A+B

1 = C-A-B

2 = C+A-B

3 = A*B/C

4 = C*A/B

5 = C*(1-A/B)

0=None

1=A-Rel

2=A-Abs

3=b-Rel

4=b-Abs

5=Calc

6=Tot

6=Tot

5=Calc

4=b-Abs

3=b-Rel

2=A-Abs

1=A-Rel

0=None